3-1.Duct For Fresh Air - Technibel DSAVM93R5TA Series Installation Manual

Split system air conditioner
Table of Contents

Advertisement

Available languages

Available languages

On the front and rear side of the unit a rectangular port (with
Outlet conduct
flange) helps during duct mounting. (fig. 3-10)
Rear and front flange for the air intake. The value included in
Intake coduct
the brackets is referred to the model X18. (fig. 3-11)
Discarge air duct (optional accessory).
Contact the After Sale Service. (fig. 3-12)
Remove the filter and pour, inside the condensate drain pan,
0.5 liter of water. Start the unit checking for proper drain pump
operation. (fig. 3-13)
False ceiling
EG
Fig. 3-10
Air intake
Fig. 3-12
Fig. 3-11
Fig. 3-13
3-1
Duct for fresh air
2
1
There is a duct connection port
for drawing in fresh air.
The supplementary fan motor for outside air intake has to be supplied separately and controlled by a bipolar ON-OFF switch with
safety fuses.
Fresh air flow must be about 10% of the total air flow to avoid operating problems and noise.
, fix a ‡ 120 mm flange on the unit and connect the thermically insulated duct.
• Open the knock-out hole
• Install an outside grille with filter inspection port to prevent dust and leaves from entering and fouling the indoor unit heat
exchanger.
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dsavm183r5ta seriesDsavm123r5ta series

Table of Contents