UniPOS IFS7002R Installation Manual

Hide thumbs Also See for IFS7002R:

Advertisement

Quick Links

1. Function
Repeater IFS7002R receives and transmits data for Fire condition and Fault Condition from remote
fire control panels IFS7002 and provides information about their status:
► when the security guards stay at a different place from the location of the fire control panel
► when several fire control panels are monitored from one location
► when the fire control panel/s are monitored from several locations
2. Installation and preparing to work
The formation of closed wire loops should be avoided when the repeater peripheral devices are
installed to the repeater IFS7002R is installed as it reduces the resistance of the Repeater to
electromagnetic interferences
2.1.
Fixing
- unpack the repeater;
- install the fixing pins at the specified place (according to the template);
- fix the box to the pins through the its four holes.
2.2. Inputs and outputs description. Installation of fire control panels and other
repeaters to the repeater.
The installation of the power supply wires and the wires for CAN network is made by means of
terminals. Standard couplings are used for connecting the repeater to PC and for connection of an
external keyboard. The location of the terminals and couplings is given in drawing 1.
♦ "RS232" – Coupling for connecting the repeater to PC (Pos.1) for system setting up and traffic
control;
♦ "CAN" – Terminals for connecting CAN2.0B interface two-wire line (Pos.4). The connection to
the fire control panels and the repeaters is executed via this interface. A jumper (Pos.2) is
provided, which if installed, shunts the line by 120 ohms. A jumper is provided which could
shunt the line by 120 ohms. It is necessary if the fire control panel is a final point on the
interface line. Resistors 120 ohms should be installed at both ends of the line for the interface.
♦ "Keyboard" – Coupling for connection of an external PS2 keyboard (Pos..3) for repeater
setting up;
♦ "Power" – terminals for supply voltage to the repeater (Pos.5);
♦ "RESET" – Button to reset the repeater (Pos.6);
REPEATER
IFS7002R
INSTALLATION MANUAL
1

Advertisement

loading

Summary of Contents for UniPOS IFS7002R

  • Page 1 2. Installation and preparing to work The formation of closed wire loops should be avoided when the repeater peripheral devices are installed to the repeater IFS7002R is installed as it reduces the resistance of the Repeater to electromagnetic interferences 2.1.
  • Page 2 CAN interface function is to transmit data and receive commands from remote fire control panels IFS7002. The repeater IFS7002R receives data from all fire control panels as it indicates the occurred events by means of sound and light indications and text messages. It is also possible the remote fire control...
  • Page 3 The connection between the devices along CAN interface is executed by parallel connection of two- wire line as it should be observed the requirement potential “L” and “H” not to be crossed. The maximum distance between the end devices should be 1200 m. The recommended connecting wire cross section should not be less than: ♦...
  • Page 4 “NO” - no communication with the respective object. If the communication with a certain object is interrupted due to any reason, the repeater will indicate an error and will provide information about the device without a connection. UniPOS wishes you pleasant work!
  • Page 5 Template for the installation holes on the repeater bottom...