GENERAL DESCRIPTION
Panel repeater 7000M-L - LED zone indication ( g.1). Repeater is capable to receive all data about zone activation
re/fault from the main panel.
TECHNICAL DATA
Connecting type:
Communication interface
Max. Repeaters per panel
Current Consumption
Connection distance
Power supply
*The maximum transmission distance is bounded by the cable properties
** In case the connection shall be up to 100m far from the panel, its power supply output can be used to ensure
supplying of the repeater.
Important: Always connect shielding (screen) core to Earth terminal from one side, shown as position 6. The other side
shielding core shall be connected to terminal 16 of the rstly installed Loop controller 1 on the DIN rail.
If there is no repeater in con guration, terminate with 120 Base's RS485 port.
INSTALLATION
Unscrew the two sideways bolts;
Open the hood ( g. 3);
It is necessary to be connected the power supply cables- 27.5V
It is necessary to connect the "RS 485" communication line. Repeater RS terminals "B" and "A" ( g 3.1)
has to be connected with 7000M/7000-1MC RS terminals "B" and "A" ( g 3.2)
Note: 7000-1MC RS teminals are 13 -A and 14 -B.
Depend of count of the repeaters in the 7000M system it is necessary every repeater to have his own
hardware address. Use the Dip Switch 3.3 to set the address. WinUniCon g software must set again
this same address ( g.4).
* Please see the Instruction Manual 7000M (" Base Module preview" and ["Panel repeater (optional)"],
Instructional Manual 7000-1MC [Base-1 loop Module].
3.2
⑦ „RS 485 B"
B
⑧„RS 485 A"
A
1
10
7000M - Base Module
7000-1MC - Base / 1 loop
Bui -Leds - depend on count of the zones panel repeater zone indication can be programmed as extension of panel's zone indication by WinUniCon g parameter "dzone-ofset".
For detail information please see WinUniCon g [Instructional Manual Creating Repeater with Zonal indications] ; 7000M Instructional Manual [ Panel - Repeater Connection (RS-485)]
7000-1MC [ Panel - Repeater Connection (RS-485)]
7000M-L
REPEATER PANEL - LED INDICATION
shielded wire, twisted pair
RS485
15
50mA/27,5V
/pcs.
DC
approx. 1000m*
21.5V
- 28V
**
DC
DC
from PSU unit ( g.3.1);
DC
Base Module "RS485"
B
G
A
Addr.1
DIP switch
3.3
Manufacturer: UniPOS Ltd., 47 San Stefano Street, Pleven 5800, Bulgaria, http://www.unipos-bg.com
3.1
+ 27,5 V
DC
+
PSU
E
27,5V
DC
-
- 27,5 V
DC
Addr.1
Fig.3
Fig.1
Fig.2
Fig.4