UniPOS Repeater IFS7002R Contents 1. Introduction.......................... 2. Function..........................3. Technical data........................3.1. Performance........................3.2. Indications of registered events..................3.3. Power supply........................3.3.1. From the fire control panel connected with the repeater..........3.3.2. From external source....................... 3.4. Dimensions.......................... 3.5. Weight..........................4. Contents of delivery......................
Page 3
UniPOS Repeater IFS7002R 10.3.2. External keyboard......................10.4. Using the menus....................... 10.4.1. Menu Repeater Configuration..................10.4.2. Menu Repeater Parameters................... 10.4.2.1. Menu Network......................10.4.2.2. Menu Local Network....................10.4.3. Menu Check........................10.4.3.1. Function Display......................10.4.3.2. Menu Buttons......................10.4.4. Menu New Passwords....................10.4.4.1. Menu Level 2.......................
UniPOS Repeater IFS7002R Introduction Repeater IFS7002R is a device supplementing the range of IFS7000 series devices as it expands the potentials of systems established based on Fire Control Panel IFS7002. The device is suitable in premises where: The person, that are expected to find and initially respond to the fire condition and/or fault condition alarm are situated on different place from the location of the fire control panel/s.
Fig.1 5.1. Access levels Four levels of access to the variable indications and control functions of IFS7002R are available. 5.1.1. Access level 1 All persons who would presumably find out and react to alarm upon fault condition or fire condition have access to level 1.
Repeater IFS7002R 5.2. Conditions and indications When the repeater IFS7002R is switched on it runs an initial verification of CAN network parameters. It checks the entered fire control panels and their condition. The repeater IFS7002R operates in seven basic modes: Duty Mode, Fire Condition, Fault Condition,...
Low battery sound, followed by 3 s break 5.3. Buttons for control and indication Table 3 presents the basic means of control. Appendix 1 shows the front panel of the repeater IFS7002R. Table 3 Condition of the Access Means of control...
Page 8
UniPOS Repeater IFS7002R Condition of the Access Means of control Operation repeater level Button Enter Information and Level 1 To enter the selected menu Control Mode Information and - To enter the selected menu; Level 2 Control Mode - To execute the selected command;...
UniPOS Repeater IFS7002R Condition of the Access Means of control Operation repeater level SetUp Mode Level 3 To move the cursor one position to the right; Button To the left - To move the cursor one position to the left;...
UniPOS Repeater IFS7002R FIRE ZONES IN FIRE: > 1Phase 1 Zone 001 Building#2 Time to Phase2: 120 Entrance Time to Phase2: 145 2Phase 1 Zone 002 Building#4 Room 202 2 floor PASSWORD Outputs Enter password: _ С Mode DAY ActInp: 0000...
UniPOS Repeater IFS7002R The display shows the logo of the company-producer, information on the REPEATER IFS7002R current local time and the mode of UniPOS Ltd operation of the fire control panel (DAY or NIGHT), the mode of control (Rep –...
Page 12
UniPOS Repeater IFS7002R For this condition the display is divided FIRE CONDITION ZONES IN FIRE: into three text panels, shown on fig.1 > 1 Phase 2 Zone 001 REM #2 Zone 001 Time Fire Phase2: 120 3 Phase 1 Zone 002 REM #4 •...
UniPOS Repeater IFS7002R Sequence number of the indicated Fire condition Phase of Fire condition Zone number Remote fire control panel address Number of zones in Fire condition Text message for the respective zone FIRE CONDITION ZONES IN FIRE CONDITION The remaining time in seconds before >...
Page 14
UniPOS Repeater IFS7002R Press it twice to suppress the Fire condition. activated local sounders of the Button is active again when connected fire control panels. registering new fire or fault in connected fire control panels. Press the button to force transition The button act once.
Fire condition.. 7.4. Example In a network built of 2 repeaters IFS7002R and 5 fire control panelsIFS7002 (Appendix4) have been reported as a response detectors. In a fire condition are different zones of the plants in the "Building#2” and "Building#4".
UniPOS Repeater IFS7002R FIRE ZONES IN FIRE: >1 Phase1 Zone 001 Building#2 Time Fire Phase 2: 068 Zone 001 3 Phase1 Zone 002 Building#4 Time Fire Phase 2: 080 Zone 002 PASSWORD Outputs Enter password: _ С Mode DAY REP...
UniPOS Repeater IFS7002R - Fault condition in a device. - Activated isolator of a device. - Activated isolator at the Power loop of a device. - Contaminated fire detector (for optical –smoke detectors). - Communication error. - Device not initialized (detected new device in a loop).
UniPOS Repeater IFS7002R 8.2.2. Text messages • Upon fatal system errors the following information screen is displayed (the first line of text messages information intended for the service staff): Fault condition Restart, please The screen suppresses all other text indications suppressed.
UniPOS Repeater IFS7002R 8.4. Example In a network built of 2 repeaters IFS7002R and 5 fire control panels IFS7002 (Appendix4) are registered following faults: - Fault in repeater IFS7002R ("Security") - Failure in communication with the remote fire control panel.
UniPOS Repeater IFS7002R Menu "List / Faults / Total" (Appendix 2) provides specific information about any damage. They are displayed in order of their occurrence. The screen shows information about REPEATER IFS7002R this example: Faults total – 3. UniPOS The first fault is in Zone 003 of Building #4.
Page 21
UniPOS Repeater IFS7002R Access Button Action Level - To execute a selected command Level 3 - Store the modified parameter Levels “Down” 1 and 2 To display the next menu item Level 3 Levels “Up” 1 and 2 To display the previous menu item...
UniPOS Repeater IFS7002R Access Button Action Level С Levels “Clear” To delete a character pointed by the cursor (if characters is pointed, 1 and 2 the first character to the left of the cursor will be deleted) Level 3 Levels...
UniPOS Repeater IFS7002R Menu “Tests” Menu “Messages from the inputs” Menu “Activated outputs” Screen “Repeater configuration” Menu “Repeater parameters” Menu “Loops” Menu “Zones” Menu “Devices status” Menu “Inputs” Menu “Archive” Menu “Choice Rep/Rem control panel” LISTS SYSTEM SET UP (9.4.1)
Page 24
UniPOS Repeater IFS7002R • The menu “All” is with two REPEATER IFS7002R variants: When there are no faults (or faults UniPOS from the searched type) if you choose menu “All” on the display appears: List/Faults/Total NO FAULTS Mode: DAY ActInp: 0000...
UniPOS Repeater IFS7002R The screen shows the connected Repeater IFS7002R objects and prides information: CAN Address UniPOS Object Name Status Faults List CAN Objects Fires Total connected CAN objects: 6 Disabled outputs The symbol “>>” is on posiiton of the...
Page 26
UniPOS Repeater IFS7002R 9.4.1.3.1. Menu “Network” This menu provides information on the parameters of RS232- netwroks: Rate, [bits/s] – data exchange rate. REPEATER IFS7002R Address in network. UniPOS Connection via modem – information if the communication is executed by means of a modem. “Yes” or RS-network parameters “No”...
UniPOS Repeater IFS7002R 9.4.1.3.2.2.Menu “CAN Objects” – REPEATER IFS7002R allows CAN parameters of the fire control panels connected UniPOS repeater to be reviewed. CAN object parameters Name CAN object Fire ControlPanel 002 Priority communication level: Slave CAN communication port: CAN...
Page 28
UniPOS Repeater IFS7002R 9.4.2.1. Function “Set Clock” The function is used to set the real time clock of the repeater to the REPEATER IFS7002R correct time. Enter the function to UniPOS display the screen: Calendar date Day of the week...
UniPOS Repeater IFS7002R While changing the values in the bottom left section appears the reminder Data not saved. • Exit the screen without saving changes and transition to the previous menu - button • Exit the screen without saving changes and transition to the Duty Mode - button •...
UniPOS Repeater IFS7002R 9.4.3. Menu Set Up Access to Set Up menu is allowed at Access Level 3; accordingly REPEATER IFS7002R as soon as you enter the menu, a UniPOS password screen appears: • Password is entered with the numeric keys - 0 ÷ 9.
UniPOS Repeater IFS7002R It discontinues the service of the fire control panels connected to it. The repeater can be controlled via the keypad provided for the purpose. The displayed screens have a tree structure of subordinate menus (Appendix 2b). To exit the condition use button (“Exit”) or press repeatedly button...
UniPOS Repeater IFS7002R The buttons (“Up”) and (“Down”), when the menu appears as ascending window from the left bottom corner of the screen. The buttons (“Move Up”) and (“Move down”) – when the menu appears on a panel in the middle of the screen.
Page 33
UniPOS Repeater IFS7002R If no external keyboard is integrated in the control panel use the buttons shown on the display for the specific menu: To edit the text use the buttons having symbols. More than one symbol is Repeater assigned to the buttons from 1 to 9.
Page 34
UniPOS Repeater IFS7002R 10.3.2. External keyboard If an external keyboard is included to the fire control panel the following screen appears: To edit the text use the buttons having symbols – when you press a button, the symbol appears over the...
UniPOS Repeater IFS7002R Repeater configuration (10.4.1) Network (10.4.2.1) CAN local object name Repeater parameters (10.4.2.2.1) (10.4.2) Local Network CAN local parameters Add new CAN object SetUp (10.4.2.2) (10.4.2.2.2) (10.4.2.2.3.1) (10) Display CAN objects Del CAN object (10.4.3.1) (10.4.2.2.3) (10.4.2.2.3.2) Checks List/Change CAN object (10.4.3)
UniPOS Repeater IFS7002R 10.4.2.1. Menu Network Use this Repeater configuration (10.4.1) menu to set Network CAN local object name (10.4.2.1) up the Repeater parameters (10.4.2.2.1) parameters (10.4.2) Local Network CAN local parameters Add new CAN object of RS232- SetUp (10.4.2.2) (10.4.2.2.2)
UniPOS Repeater IFS7002R Use this menu to set up CAN parameters of the repeater and CAN parameters of the fire control panels connected to it that should be entered in the repeater. The setting is needed to unique determine the parameters of the connected objects.
UniPOS Repeater IFS7002R 10.4.2.2.2. Menu CAN Local parameters Repeater configuration (10.4.1) Network (10.4.2.1) CAN local object name Repeater parameters (10.4.2.2.1) (10.4.2) Local Network CAN local parameters Add new CAN object SetUp (10.4.2.2) (10.4.2.2.2) (10.4.2.2.3.1) (10) Display CAN objects Del CAN object (10.4.3.1)
Page 39
UniPOS Repeater IFS7002R successful check repeater connection with the subsequent fire control panel connected to it: If the value is 0 - no “Beep” is released If the value is N>0, each N successful check is signaled by “beep”. For example, if it is entered N=1, each check- performed at each “Period of...
Page 40
In IFS 7000 series the devices share a common address space. The maximum number of repeaters and fire control panels UniPOS connected in CAN network is 32. The name is of importance only for the user and an object having a local name might be assigned another name suitable for user when it is added to the list of local objects.
Page 41
UniPOS Repeater IFS7002R Repeater configuration (10.4.1) Network (10.4.2.1) CAN local object name Repeater parameters (10.4.2.2.1) (10.4.2) Local Network CAN local parameters Add new CAN object SetUp (10.4.2.2) (10.4.2.2.2) (10.4.2.2.3.1) (10) Display CAN objects Del CAN object (10.4.3.1) (10.4.2.2.3) (10.4.2.2.3.2) Checks (10.4.3)
Page 42
UniPOS Repeater IFS7002R • Enter the name of the Set Up Add New CAN Object added CAN object in submenu Name New CAN object is added to the repeater CAN Object (Example: “Building#1”). Total connected CAN objects: 3 >> Name CAN object Parameters CAN object Communic.
Page 43
UniPOS Repeater IFS7002R - Fires, Faults Communication options Object Fire, Fault CAN local object name: Building #1 Receive Fire Info: Set Rell/Receive Fires: Yes Send Fire Commands: Yes Send Fire Info: Yes Receive Fire Commands: Yes Receive Faulst Info: Yes...
Page 44
UniPOS Repeater IFS7002R - Setup, System Communication Options Object SetUp, System CAN local name object: Building #1 Receive ‘SetUp’ Requests: Send ‘SetUp’ Requests: Yes Receive ‘Init’ Requests: Yes Send ‘Init’ Requests: Yes Receive ‘Sys/Disables’ Requests: Yes Send ‘Sys/Disables’ Requests: Yes Receive ‘Sys/Mode’...
Page 45
UniPOS Repeater IFS7002R 10.4.2.2.3.2. Menu Delete CAN Object Use this menu to delete CAN objects connected to the repeater. Repeater configuration (10.4.1) Network (10.4.2.1) CAN local object name Repeater parameters (10.4.2.2.1) (10.4.2) Local Network CAN local parameters Add new CAN object SetUp (10.4.2.2)
Page 46
UniPOS Repeater IFS7002R Use this menu to delete CAN Set Up Delete CAN Object objects connected to the repeater. When the menu is selected a Total connected CAN objects: 3 window appears containing a list of the CAN objects connected to the repeater: >>...
Page 47
UniPOS Repeater IFS7002R Repeater configuration (10.4.1) Network (10.4.2.1) CAN local object name Repeater parameters (10.4.2.2.1) (10.4.2) Local Network CAN local parameters Add new CAN object SetUp (10.4.2.2) (10.4.2.2.2) (10.4.2.2.3.1) (10) Display CAN objects Del CAN object (10.4.3.1) (10.4.2.2.3) (10.4.2.2.3.2) Checks (10.4.3)
UniPOS Repeater IFS7002R 10.4.3. Menu Checks The menu allows the user to set up the display and the buttons. It contains the following submenus and functions: − Menu “Monitored outputs” − Menu “Relay outputs” − Menu “Addressable outputs” − Function “Display”...
Page 49
UniPOS Repeater IFS7002R Repeater configuration (10.4.1) Network (10.4.2.1) CAN local object name Repeater parameters (10.4.2.2.1) (10.4.2) Local Network CAN local parameters Add new CAN object SetUp (10.4.2.2) (10.4.2.2.2) (10.4.2.2.3.1) (10) Display CAN objects Del CAN object (10.4.3.1) (10.4.2.2.3) (10.4.2.2.3.2) Checks (10.4.3)
Page 50
UniPOS Repeater IFS7002R To start setting the buttons up, + Push the Point of intersection press button . Set up is being performed at two points on the display and is being checked at two points. Enter the function to...
UniPOS Repeater IFS7002R 10.4.4. Menu New Passwords The menu allows the user to compose and edit passwords for Access Level 2 and 3. It contains: − Menu “Level 2” − Menu “Level 3” − Menu “Options” Repeater configuration (10.4.1) Network CAN local object name (10.4.2.1)
10.4.4.3. Menu Options In IFS7002R an option is provided possible to use button (“Outputs”) at Access level 1. Button is displayed when the repeater is in Fire condition and served to suppress/enable outputs in the connected Fire control panel.
UniPOS Repeater IFS7002R 10.4.5. Function “Default parameters” The function saves the default parameters of the repeater Repeater configuration (10.4.1) Network (10.4.2.1) CAN local object name Repeater parameters (10.4.2.2.1) (10.4.2) Local Network CAN local parameters Add new CAN object SetUp (10.4.2.2) (10.4.2.2.2)
UniPOS Repeater IFS7002R Upon unsuccessful operation Default Parameters appears the following screen: Operation unsuccessful! Would you like to run the Operation again? – confirm – cancel Mode DAY 09:43:50 Wed 24 Aug 2011 When the records are successfully saved, the menu is exited automatically.
UniPOS Repeater IFS7002R 13. Installation and arrangements When installing the repeater and connecting it to fire control panels and repeaters integrated in the fire detecting system, avoid arranging wires in closed loops; it will reduce the resistance of the repeater to electromagnetic interferences.
− the conditions of storage and transportation have been observed; − the startup has been done by authorized personnel by the producer. − the requirements for operation stated herein have been observed. UniPOS wishes you a successful work! UniPOS 47, “San Stefano” Str., 5800 Pleven, BULGARIA phone +359 64 891111, +359 64 891 100, fax +359 64 891 110 e-mail: office_pleven@unipos-bg.com...
Common indicator for fault condition Indicator for System error Indicator for Fault in power supply Indicator for Disabled component Test indicator Indicator for Power supply LCD display Front panel of repeater IFS7002R Instruction Manual Page 57 Revision 2/16.11.09 Of 62...
Page 58
UniPOS Repeater IFS7002R Appendix 2 Fire Duty mode Automatic condition Main screen Lists System functions SetUp Total Zones Password level 3 Password level 2 Faults Devices Appendix 2b Outputs LAN object Disables Zones Total Devices Disables Zones Outputs Test zones...
Page 59
UniPOS Repeater IFS7002R Appendix 2 continued SetUp CAN local object name Password level 3 CAN local paramaeters Network CAN objects Repeater Local network configuration Loop parameters Devices parameters Repeater Devices list paramaters Check Loop1 Manual addressation Loops Loop parameters Devices parameters...
Page 60
UniPOS Repeater IFS7002R Appendix 2 continued From part 1 List of Addressable outputs Delete Addressable output Add Addressable output Inputs Mode of outputs activation Text message Initialization Clean initialization Initialization Readdressation Turn off the devices Check Controllable outputs Relay outputs...
Page 61
UniPOS Repeater IFS7002R Appendix 3 Power Instruction Manual Page 61 Revision 2/16.11.09 Of 62...
Page 62
UniPOS Repeater IFS7002R Appendix 4 1. Menu “Setup/Repeater configuration” (item 10.4.1) Local network: Periphery Device 1: Periphery Device 2: Periphery Device 3: Power Loop: Language: English 2. Configuration panel parameters “Repeater parameters” (item 10.4.2). 2.1. Menu “Setup/Repeater parameters/Network” (item 10.4.2.1).
Need help?
Do you have a question about the IFS7002R and is the answer not in the manual?