Error Codes When Performing A Test Run; Disposal; Technical Data; Piping Diagram: Indoor Unit - Daikin FCAG35BVEB Installation And Operation Manual

Hide thumbs Also See for FCAG35BVEB:
Table of Contents

Advertisement

#
Action
2
Select Test Operation.
3
Press.
6.3
Error codes when performing a
test run
If the installation of the outdoor unit has NOT been done correctly,
the following error codes may be displayed on the user interface:
Error code
Nothing displayed
▪ The wiring is disconnected or there is a
wiring error (between power supply and
(the currently set
outdoor unit, between outdoor unit and
temperature is not
indoor units, between indoor unit and
displayed)
user interface).
▪ The fuse on the outdoor or indoor unit
PCB has blown.
E3, E4 or L8
▪ The stop valves are closed.
▪ The air inlet or air outlet is blocked.
E7
There is a missing phase in case of three-
phase power supply units.
Note: Operation will be impossible. Turn
OFF the power, recheck the wiring, and
switch two of the three electrical wires.
L4
The air inlet or air outlet is blocked.
U0
The stop valves are closed.
U2
▪ There is a voltage imbalance.
▪ There is a missing phase in case of
three-phase power supply units. Note:
Operation will be impossible. Turn OFF
the power, recheck the wiring, and switch
two of the three electrical wires.
8.2

Wiring diagram

8.2.1

Unified wiring diagram legend

For applied parts and numbering, refer to the wiring diagram on the
unit. Part numbering is by Arabic numbers in ascending order for
each part and is represented in the overview below by "*" in the part
code.
Symbol Meaning
Symbol
Circuit breaker
Connection
A
,
Connector
Earth
Field wiring
Fuse
Indoor unit
INDOOR
Outdoor unit
OUTDOOR
FCAG35~140BVEB
Split system air conditioners
4P535626-1C – 2019.09
Result
Service Settings
1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
Return
Setting
The unit returns to normal
operation, and the home
menu is displayed.
Possible cause
Meaning
Protective earth
Protective earth
(screw)
Rectifier
Relay connector
Short-circuit
connector
Terminal
Terminal strip
Wire clamp
Error code
U4 or UF
The inter-unit branch wiring is not correct.
UA
The outdoor and indoor unit are
incompatible.
7

Disposal

NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
8

Technical data

▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of latest technical data is available on the Daikin
Business Portal (authentication required).
8.1

Piping diagram: Indoor unit

c
a
b
a
Liquid pipe connection
b
Gas pipe connection
c
Heat exchanger
Symbol
Colour
Symbol
BLK
Black
ORG
BLU
Blue
PNK
BRN
Brown
PRP, PPL
GRN
Green
RED
GRY
Grey
WHT
YLW
Symbol
A*P
BS*
BZ, H*C
C*
AC*, CN*, E*, HA*, HE*, HL*,
HN*, HR*, MR*_A, MR*_B, S*, U,
V, W, X*A, K*R_*
D*, V*D
DB*
7 Disposal
Possible cause
Colour
Orange
Pink
Purple
Red
White
Yellow
Meaning
Printed circuit board
Pushbutton ON/OFF, operation
switch
Buzzer
Capacitor
Connection, connector
Diode
Diode bridge
Installation and operation manual
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents