3 IFC CABLE ROUTING AND INSTALLATION

This section provides instructions for routing an IFC cable through an NG3 frame and installing
the cable in the appropriate NG3 panel. If the IFC cable is pre-installed in the panel, disregard
subsections 3.2 through 3.4. IFC cables may be of stranded or ribbon type construction.
3.1
General IFC Cable Routing Guidelines–All Panel Types
IFC cables are routed to the rear side of the frame from either above or below the NG3 panel.
Each IFC cable is routed vertically up or down the left rear side of the frame to the designated
panel as shown in
rear of the designated panel and into the opening on the right rear side of the panel. A clamp
secures the IFC cable to the rear side of the panel. The cable should also be secured to the frame
using wax lacing tied to the tie down bars located on the left rear side of the frame.