SensControl Lighting management
Setting lockout and automatic control
Setting burn-in mode

Stand-by operation

Article no.: 00109607/PC 01.17
Activating/deactivating lockout
1.
Press both keys simultaneously and hold for 8 seconds.
a LED lights up.
2.
Briefly release both keys and press again simultaneously, holding for 5 seconds.
a LED flashes slowly.
3.
Press upper key 5 times to deactivate the lockout.
- or -
Press upper key 6 times to activate the lockout.
a LED flashes 5 or 6 times to confirm.
4.
Press both keys simultaneously and hold for 8 seconds to permanently save the
setting.
a The LED extinguishes.
Switching between fully automatic and semi-automatic control
1.
Press both keys simultaneously and hold for 8 seconds.
a LED lights up.
2.
Briefly release both keys and press again simultaneously, holding for 5 seconds.
a LED flashes slowly.
3.
Press upper key 1 time to activate semi-automatic control.
- or -
Press upper key 2 times to activate fully automatic control.
a LED flashes 1 or 2 times to confirm.
4.
Press both keys simultaneously and hold for 8 seconds to permanently save the
setting.
a The LED extinguishes.
Activating, deactivating and resetting burn-in
1.
Pull out the power plug and plug in again with the upper key held down.
a The LED lights up briefly and is then extinguished for an extended period.
2.
The burn-in mode ends automatically after 100 hours.
a The LED no longer flashes.
3.
To deactivate the burn-in mode (switch off temporarily), pull out the power plug and
plug in again with the upper key held down.
a The 100-hour counter is stopped, the burning-in process can be resumed later on,
the LED no longer flashes.
4.
To reset the burn-in mode (switch off permanently), perform a factory reset (pull out
the power plug and plug in again with the lower key held down).
a The LED no longer flashes.
The LED lights up in stand-by operation to indicate the functional integrity of the
luminaire. Power consumption in stand-by operation is < 0.2 W.