TMM-1
PIM-1
switch S1 to set the network address of the
MKB-3. Refer to Table 3 for switch settings.
2. The MKB-3 module address is always set
within network addresses 248 through 251.
3. One supervised MKB-3 must be installed
at network address 251. Other supervised
MKBs may be at the other addresses.
NOTE: Switches S1-SW3 and S1-SW4 are for
future use. Switch S1-SW5 is used to
select supervision.
Setting Supervision
Use switch S1-SW5 on the ANN-1 to select or
deselect supervision. If your ANN-1 has a switch
with position 1 indicated on the left-hand side,
ignore the printing on the switch. SW1 on S1 is at
the extreme right-hand side of S1, regardless of
any other marking.
To set for supervision
S1-SW5 = Closed (ON)
To set for non-supervision
S1-SW5 = Open (OFF)
TBM-2
P7
P8
P6
EXTENSION FROM
TO ANN-1
CABLES-RK KIT
(MKB-RK)
NEW CABLE FROM
CABLES-RK KIT
ACM-1
P4
P5
TO MMB-2
NEW CABLE FROM
CABLES-RK KIT
P1
P3
EXISTING
MMM-1 CABLE
MMM-1
ACM-RK
NOTE: When you select non-supervision for an
annunciator, there must also be one and
only one supervised annunciator at the
same address. The supervisory mode is
independent of the network address.
SWITCH SETTINGS ON THE ANN-1
ADDRESS SETTINGS FOR:
SWITCH
248
Open-
S1-SW1
OFF
Open-
S1-SW2
OFF
Closed-
S1-SW3
ON
Closed-
S1-SW4
ON
S1-SW5
See Setting Supervision
3
Figure 2
Rear View of the ACM-RK
TABLE 3
249
250
251
Closed-
Open-
Closed-
ON
OFF
On
Open-
Closed-
Closed-
OFF
ON
ON
Closed-
Closed-
Closed-
ON
ON
ON
Closed-
Closed-
Closed-
ON
ON
ON