Technical Data - S+S Regeltechnik PREMASREG 711 Series Operating Instructions, Mounting & Installation

Pressure and differential pressure measuring transducers/switches, incl. connection set, with multi-range switching and adjustable, switching and active output.
Hide thumbs Also See for PREMASREG 711 Series:
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 10
G
®
PREMASREG
711x
The electronic PREMASREG
®
one continuous output, and a display for setting the switchpoint and to display the ACTUAL pressure (eight devices in one, plus differential pressure
switch ⁄ differential pressure monitor, continuous pressure sensor in a single device). The pressure sensor is used for above-atmospheric,
below-atmospheric, or differential pressure measurement in clean air with limit value switching. The piezo-resistive measuring element guarantees
a high degree of reliability and accuracy. Applications of these pressure sensors are in clean room, medical and filter technology, in ventilation and
air conditioning ducts, in spray booths, in large-scale catering facilities, for monitoring filters, for level measurement or for triggering frequency
converters. Media measured with these pressure transducers are air (non-precipitating), or other gaseous non-aggressive, non-combustible media.
The pressure sensor has a manual zero point pushbutton and an offset potentiometer for final value and switchpoint correction. Fine adjustment by
the user is possible at any time. The delivery includes the connection set ASD-06 (2 m connection hose, two pressure connection nipples, screws).

TECHNICAL DATA

Voltage supply:
Load resistance:
Power consumption:
Measuring ranges:
Output signal:
Electrical connection:
Media temperature:
Pressure connection:
Type of pressure:
Medium:
Accuracy:
Sum of
Linearity+hysteresis:
Temp. drift values:
Zero point offset:
Above- ⁄ below-atmospheric
pressure:
Signal filtering:
Setting increment Δp:
Switching hysteresis:
Enclosure:
Dimensions:
Electrical connection:
Cable gland:
Air humidity:
Protection class:
Protection type:
Standards:
Equipment:
ACCESSORIES
ASD - 06
ASD - 07
DAL-01
WS-03
711x pressure sensors and switches are equipped with eight switchable measuring ranges, one switching output and
24 V AC ⁄ DC (± 20 %)
R
> 5 kOhm
L
< 1 VA ⁄ 24 V DC, < 2.2 VA ⁄ 24 V AC
multi-range switching
with 8 switchable measuring ranges (see table)
0 -10 V
1 changeover contact (24 V), 1 A ohmic load
3-wire connection (U)
–20...+50 °C
4 ⁄ 6 x 11 mm (hoses Ø = 4 ⁄ 6 mm),
metal pressure connection nozzles
differential pressure
clean air and non-aggressive, non-combustible gases
Type 7111 (1000 Pa): ± 5 Pa
Type 7115 (5000 Pa): ± 25 Pa
compared to the calibrated reference device
< ± 1 % of final value
± 0.1 % ⁄ °C
< ± 0.7 % of final value
max. ± 100 hPa
switchable 1 s ⁄ 10 s
1 % of pressure range (100 Pa => 1 Pa; 5000 Pa => 50 Pa)
± 1 % of pressure range (100 Pa => ± 1 Pa; 5000 Pa => ± 50 Pa)
plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016), enclosure cover for display is transparent!
126 x 90 x 50 mm (Tyr 2)
0.14 - 1.5 mm², via plug-in screw terminal
M 16 x 1.5; including strain relief
< 95 % r. H., non-precipitating air
III (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity according to EMC Directive 2014 ⁄ 30 ⁄ EU,
according to EN 61326-1, according to EN 61326-2-3
three-line display with illumination, cutout approx. 70 x 40 mm (W x H),
for displaying ACTUAL pressure and ⁄ or SETPOINT pressure
and for adjusting the automatic zero point calibration
Connection set (nipple straight) – (included in the scope of delivery)
Connection nipple (at 90° angle)
Pressure outlet for ceiling or in-wall installation (e.g. in clean rooms)
Weather and sun protection, 200 x 180 x 150 mm, stainless steel
10