Split unit air conditioner
ceiling mounted c series; e series; fl-e series; fh-c series; fly-e series; fhy-c series
cooling only & heatpump [50hz] (78 pages)
Si241313 Table of Contents 1. Procedure to Remove Outside Panels............2 2. Procedure to Remove Propeller Fan and Fan Motor ......3 3. Procedure to Remove El. Compo. Box ...........4 4. Procedure to Remove Reverse Phase Protector ........5 5. Procedure to Remove Compressor............6 Removal Procedure...
Procedure to Remove Outside Panels Si241313 1. Procedure to Remove Outside Panels Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Procedure Points Step Pull the lower part (7 positions) of suction grille to your side and dismount 2 screws,...
Si241313 Procedure to Remove Propeller Fan and Fan Motor 2. Procedure to Remove Propeller Fan and Fan Motor Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Removing top panel and front panel according to...
Procedure to Remove El. Compo. Box Si241313 3. Procedure to Remove El. Compo. Box Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Procedure Points Step Removing top panel and front panel according to the “Procedure to Remove Outside Panels”.
Si241313 Procedure to Remove Reverse Phase Protector 4. Procedure to Remove Reverse Phase Protector Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Procedure Points Step Removing top panel and front panel according to the “Procedure to Remove Outside Panels”.
Procedure to Remove Compressor Si241313 5. Procedure to Remove Compressor Procedure Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Procedure Points Step Removing top panel and Check that the refrigerant is front panel according to completely discharged Stop valve...
Page 9
Revision History Month / Year Version Revised contents 01/2013 Si241313 First edition...
Page 10
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.