Page 1
Operating manual REMKO Smart-Control Touch For the heat pump series HTS, WKF, WKF-compact, WKF NEO LWM and LWM Duo Specialist and user manual 0203-2019-09 Edition 3, en_GB Read the instructions prior to performing any task!
Page 2
Read these operating instructions carefully before commis- sioning / using this device! These instructions are an integral part of the system and must always be kept near or on the device. Subject to modifications; No liability accepted for errors or mis- prints! Translation of the original operating manual...
Table of contents Safety and usage instructions......................4 1.1 General safety notes........................4 1.2 Identification of notes........................4 1.3 Personnel qualifications........................4 1.4 Dangers of failure to observe the safety notes................4 1.5 Safety-conscious working....................... 4 1.6 Safety notes for the operator......................5 1.7 Safety notes for installation, maintenance and inspection..............
REMKO Smart-Control Touch Safety and usage instructions CAUTION! This combination of symbol and signal word 1.1 General safety notes warns of a potentially hazardous situation, which if not avoided may cause injury or mate- Carefully read the operating manual before com- rial and environmental damage.
The setup, connection and operation of the plete and return the "certificate of warranty" to units and its components must be undertaken REMKO GmbH & Co. KG at the time when the in accordance with the usage and operating units are purchased and commissioned.
REMKO Smart-Control Touch 1.11 Transport and packaging The devices are supplied in a sturdy shipping con- tainer or inside the heat pump casing. Please check the equipment immediately upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contrac- tual partner.
Technical data Series Smart Control Touch Operating mode Remote control Power supply +12 V DC Enclosure class Power consumption < 100 Max. cable length Recommended cable 2 x 0,5 Dimensions Height Width Depth Environment Ambient temperature °C 0-70 Air humidity % rH 0-95 (relative) non-condensing Remote control EDP no.
Selecting user/expert mode General notes You can access the expert level by touching the REMKO logo in the upper right corner of the dis- Overview of the controls play. After entering the password (0321) using the +/- combination and then touching the "Next" and "OK"...
Page 9
Scroll up in the screen to enter the "Overview" Navigation in the overview menu item level from the basic display. You will find the fol- lowing submenus here: Room climate mode The operating mode for the room heating can be changed here. Colder/warmer The desired room temperature can be adjusted here.
REMKO Smart-Control Touch Operation - User level 4.1 Menu structure Übersicht Übersicht Übersicht Information Information Information Einstellungen Einstellungen Einstellungen Meldungen Meldungen Meldungen Overview Information Settings Messages Raumklima- Raumklima- Raumklima- Grund- Grund- Grund- Grund- Grund- Grund- Fehlermeldungen Fehlermeldungen Fehlermeldungen Room Basic...
Page 11
In the settings menu item it is possible to adjust parameters for the enabled components. Here, you have the option of adjusting e.g. heating curves in accordance with the requirements the REMKO heat pump user. Relevant points that affect the safety of the complete system are only to be changed by a specialist.
Page 12
REMKO Smart-Control Touch "Information" menu item - User This menu contains information about the current operating status of the system. Level 2 menu item Level 3 menu item Level 4 menu item Detected unit Current operating mode Previous operating mode...
Page 13
"Information" menu item (continued) - User Level 2 menu item Level 3 menu item Control signal A01 Collector temperature S01 Storage tank temperature, bottom S02 Storage tank charging status Solar Current output Solar yield Medium flow rate S23 Stored energy Hot water demand Hot water storage tank target temperature Hot water storage tank actual temperature S08...
Page 14
REMKO Smart-Control Touch "Information" menu item (continued) - User Level 2 menu item Level 3 menu item Operating mode Set temperature Actual temperature Room set temperature 1st mixed cycle Room actual temperature Room humidity Dew point Mixed outside temperature Operating mode...
Page 15
"Information" menu item (continued) - User Level 2 menu item Level 3 menu item Heat generator request Hot water temperature (setpoint) Hot water temperature (actual value) Power, thermal Changeover valve 2nd heat generator A11 Changeover valve A14 Hydraulics Pump speed rel. A43 Pump speed rel.
Page 16
REMKO Smart-Control Touch "Information" menu item (continued) - User Level 2 menu item Level 3 menu item Heat pump status Remaining idle time Defrost status Compressor status Compressor frequency Fault status Fault code (outdoor) Heat pump Fault code (indoor) (I/O 2/HP 2)
Page 17
"Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Level 4 menu item Current output Solar Solar yield Thermal power, heat pump Thermal energy, heat pump Electrical power, heat pump Heat pump Electrical energy, heat pump Output, environment Environmental energy Current household output...
Page 18
REMKO Smart-Control Touch "Settings" menu item - User In this menu you can configure the settings. For example, you can adjust hot water and heating tempera- tures or change time settings. Level 2 menu item Level 3 menu item Level 4 menu item...
Page 19
"Settings" menu item (continued) - User Level 2 menu item Level 3 menu item Level 4 menu item Room climate mode Mode Difference from cooling limit Difference from heating limit Heating/cooling Standard outside temp. (Heating) Building adaptation Standard outside temp. (Cooling) Inertia of the heating curve Operating mode Heating cycle mode...
Page 20
REMKO Smart-Control Touch "Settings" menu item (continued) - User Level 2 menu item Level 3 menu item Level 4 menu item Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment 1st mixed...
Page 21
"Settings" menu item (continued) - User Level 2 menu item Level 3 menu item Level 4 menu item Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment 3rd mixed Time program A cycle Time program B Time program C...
Page 22
REMKO Smart-Control Touch "Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Level 4 menu item Number of power tariffs Heat pump Graduated tariff Time field Tariff 1-9 Power tariff 1-9 Power tariff 1 PV current...
4.2 Setting the heating/cooling operating mode Heating curve heating cycle mode The heating curve can be adjusted in three points, according to the structure and location-related con- ditions of the building: Base point: The base point corresponds to the minimum set temperature of the heating water at an outside temperature of 20 °C.
Page 24
REMKO Smart-Control Touch Setting the heating curve: 2. Standard inlet temperature 1. Base point The standard inlet temperature is set using the same procedure. In this level, select the heating cycle to be changed and select the parameter "Heating curve settings".
Page 25
The mixed heating cycles each require a supply and return probe! These probes are included in the scope of supply of the mixed REMKO heating cycle groups. Fig. 9: Set the standard outside temperature The standard outside temperature [1] can be changed for the user and the expert.
Page 26
REMKO Smart-Control Touch Activation of the cooling function via the unmixed cycle This is where you can select between the different cooling cycle modes. The choice is between con- trol according to the set "cooling curve" and "fixed value regulation".
Page 27
Fig. 13: Setting the inlet temperature A cooling function via the cooling curve setting Fig. 12: Setting the base point is only enabled by REMKO if the corresponding humidity probe is installed! NOTICE! At least one dew point monitor with corre- sponding probes should be installed to protect the system in the case of panel heating.
Page 28
(e.g. if the ating mode is set from "Automatic" to "Cooling". underfloor system is to be cooled). REMKO recom- mends protecting the system with dew point moni- tors in the case of panel heating.
Page 29
CAUTION During cooling mode via the underfloor/panel heating system, make sure that the dew point is not undershot. REMKO recommends installing dew point probes in conjunction with one (max. five probes for dew point monitoring) or more dew point monitors.
Heating limit The heat pump, circulation pumps and heating sur- The heating limit of the Smart-Control Touch con- faces are constantly in operation, in order to keep troller is coupled with the room set temperature via all rooms at the desired temperature.
Page 31
In order to specify the point of the summer/winter changeover, you must first determine the value "colder/hotter" because this is coupled with the heating limit temperature. Fig. 18: Select "colder/hotter" menu item The "colder/hotter" parameter is displayed in the "Basic display". This parameter is used to calculate the desired target room temperature.
Page 32
REMKO Smart-Control Touch Now proceed as follows in the parameter level "heating/cooling" Fig. 21: Select "Settings" menu item Fig. 20: Start screen...
Page 33
Fig. 22: Select "Heating/cooling" menu item Fig. 23: Select "Mode" menu item In the "heating/cooling" parameter level you must select the "Mode" level. In the "Mode" parameter level you will find the "Dif- ference from heating limit" parameter. Set the desired value at which the heating opera- tion of the heat pump should be switched off.
Page 34
REMKO Smart-Control Touch The building time constant is preset by REMKO in the factory at 10 hours. Setting the building time constant should prevent the heat pump from cycling. The better the building standard, the longer the possible setting of the building time con- stant.
4.4 WLAN function The central controller for the REMKO heat pump via a smart phone or other mobile devices can be Installation and setup of the WLAN function installed virtually anywhere in the building. System requirements The connection requires a router which is con-...
Page 36
Once you have finished entering the password This is only possible at the expert level. To do so, (0321), confirm the input with "OK". touch the REMKO logo in the upper right corner of the display. Fig. 27: Password input...
Page 37
The REMKO default password for the expert level Select the "Settings" level here by touching it. is "0321". If this password has not already been changed, the expert level is enabled after entering this password. Fig. 29: Select "Settings" menu item...
Page 38
REMKO Smart-Control Touch After selecting the "Settings" level, select the The "Interfaces" parameter appears in the "Basic "Basic settings" parameter. settings" level. Touch to select this. Fig. 30: Select "Basic settings" menu item Fig. 31: Select "Interfaces" menu item...
Page 39
In the "Interfaces" parameter level you will find the In the "Network" level, you can now connect the "Network" parameter. Touch to select this param- heat pump with your router. To do so, first select eter. the "Authentication" parameter. ******** (....) Fig.
Page 40
"Selection" parameter. When appropriate parameter for your WLAN network. doing so you can choose between upper and lower Note that the REMKO Smart-Control Touch only case letters, numbers or special characters such supports the WPA 2 encryption/security standard.
Page 41
To return to the basic display, exit the parameter level via the arrow at the top left or touch the basic display symbol. To connect the REMKO Smart-Control Touch with your router, the WLAN network must be received by the controller with sufficient signal...
Page 42
Smart-Con- ters for the user and expert level of your REMKO trol Touch controller. heat pump via a PC, laptop or smartphone.
"+/-" and then possible in the expert level. To do so, touch the proceed to the next item with "Next". Once you REMKO logo in the upper right corner of the dis- have finished entering the password (0321), con- play.
Page 44
REMKO Smart-Control Touch After the expert level has been enabled, various After selecting the "Settings" level, select the parameter levels are visible. "Basic settings" parameter. Select the "Settings" level here by touching it. Fig. 43: Select "Basic settings" menu item...
Page 45
The "System configuration" parameter appears in After selecting the "System configuration" level, the "Basic settings" level. Touch to select this. select the "Heat pump" parameter. Then deactivate the heat pump in the "Heat pump" level by touching "activated" and changing the operating mode setting from "activated"...
Page 46
REMKO Smart-Control Touch The heat pump is now deactivated. With deactivation of the heat pump, the second heat generator, e.g. the REMKO Smart-Serv auxil- iary heater or a condensing unit installed in the system is active. Fig. 46: Activation of a 2nd heat generator...
To enter the password at this level, use You can access the expert level by touching the "+/-" and then proceed to the next item with "Next". REMKO logo in the upper right corner of the dis- Once you have finished entering the password play.
Page 48
In the settings menu item it is possible to adjust parameters for the enabled components. Here, you have the option of adjusting e.g. heating curves in accordance with the requirements the REMKO heat pump user. Relevant points that affect the safety of the complete system are only to be changed by a specialist.
Page 49
Overview Information Settings Messages Übersicht Übersicht Information Information Einstellungen Einstellungen Meldungen Meldungen Raumklima- Raumklima- Grund- Grund- Basic Room cli- Basic Grund- Grund- Fault messages Fehlermeldungen Fehlermeldungen mate mode information settings einstellungen einstellungen modus modus informationen informationen Warnhinweise Warning notices Warnhinweise Kälter/ Kälter/ Colder/hotter...
Page 50
REMKO Smart-Control Touch "Information" menu item - Expert This menu contains information about the current operating status of the system. Depending on the heat pump installed and the design, individual parameters may vary from version to ver- sion. Level 2 menu item...
Page 51
"Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Level 4 menu item Hardware Control Panel Hardware Software Control Panel Software Software (I/O 2) Linux Kernel Control Panel Version number Linux Kernel µPC edition µPC software date Revision (HP 1) Revision (HP 2) Basic information (con-...
Page 52
REMKO Smart-Control Touch "Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Hot water demand Hot water storage tank target temperature Hot water storage tank actual temperature S08 Changeover valve A10 Hot water energy Hygiene function...
Page 53
"Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Operating mode Set temperature Actual temperature Inlet temperature S12 Return temperature S11 Room set temperature Room actual temperature 1st mixed cycle Room humidity Dew point Mixed outside temperature Pump speed rel.
Page 54
REMKO Smart-Control Touch "Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Operating mode Set temperature Actual temperature Inlet temperature S12.2 Return temperature S11.2 Room set temperature Room actual temperature 3rd mixed cycle Room humidity...
Page 55
"Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Heat generator request Hot water temperature (setpoint) Hot water temperature (actual value) Power, thermal Inlet temperature S13 (HP 1) Inlet temperature S13.2 Inlet temperature (HP 2) Inlet temperature mixed Return temperature S15 (HP 1) Return temperature (HP 2)
Page 56
REMKO Smart-Control Touch "Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Heat pump status Sub-status Remaining idle time Defrost status Compressor status Fault status Enable signal Disable compressor Heat pump status Disable signal S16, energy supplier cut-off Compressor frequency Max.
Page 57
"Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Envelope status Heat pump (HP 1) Inverter status (continued) Anti-freeze protection status Level 2 menu item Level 3 menu item Heat pump status Sub-status Remaining idle time Defrost status Compressor status Fault status...
Page 58
REMKO Smart-Control Touch "Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Overheating Compressor starts Run-time (minutes) Heat pump (I/O 2/HP 2 Run-time (hours) (continued) Envelope status Inverter status Anti-freeze protection status Only LWM and WKF Duo...
Page 59
"Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Level 4 menu item Heat generator status Potential-free output A32 Enable electric heater (HP 1) Auxiliary heat generator Enable electric heater (HP 2) Enable Enable time (minutes) Enable time (hours) Current output Solar yield, day...
Page 60
REMKO Smart-Control Touch "Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Level 4 menu item Current household output Household energy (day) Household energy (week) Household Household energy (month) Household energy (year) Household energy Photovoltaic output...
Page 61
"Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Collector temp. S01 Lower storage tank temp. S02 Inlet temperature S03 Return temp. S04 Circulation actual temperature S05 Circulation request S05 Inlet temperature S06 Inlet temperature S06.2 Refrigerant temperature S07 Refrigerant temperature S07.2 Hot water storage tank actual temperature S08...
Page 62
REMKO Smart-Control Touch "Information" menu item (continued) - Expert Level 2 menu item Level 3 menu item Impulse counter status S25 Impulse counter status S26 Checklist Medium flow rate S 27 (continued) Impulse counter S 28 Impulse counter S 29...
Page 63
"Settings" menu item - Expert In this menu you can configure the settings. For example, you can adjust hot water and heating tempera- tures or change time settings. Depending on the heat pump installed and the design, individual parameters may vary from version to ver- sion.
Page 64
REMKO Smart-Control Touch "Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Level 4 menu item Level 5 menu item Smart Com Interface search IA for the KNX interface Multicast address IA for the controller...
Page 65
"Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Level 4 menu item Level 5 menu item Unmix. HC humidity 1st mixed HC humidity. 2nd mixed HC humidity 3rd mixed HC humidity 4th mixed HC humidity Time Date Unmix.
Page 66
REMKO Smart-Control Touch "Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Level 4 menu item Heat pump Auxiliary heat generator PV current usage Graduated tariffs Domestic hot-water heating Hot water circulation Hygiene function Unmixed cycle...
Page 67
"Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Level 4 menu item Max. temperature Max. temperature hysteresis Min. temperature Collector Min. temperature hysteresis Switch-on difference Switch-off difference Solar set temperature Solar set temperature hysteresis Storage tank Collector cooling function ON temp.
Page 68
REMKO Smart-Control Touch "Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Level 4 menu item Storage tank set temperature Mode Time program A Time program B Domestic hot-water heating Time program C Tolerance during ECO operation...
Page 69
Factory-set circulation switching times Designation Value range Factory setting Customer system Time program Mon-Sun Mon-Sun 00:00-24:00 Hygiene function Designation Value range Factory setting Customer system Set temperature "60 °C - 75 °C" 60 °C Day of activation Mon-Sun Monday Time of activation Hrs/Mins 20:00 Inspection time...
Page 70
REMKO Smart-Control Touch "Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Level 4 menu item Building time constant Standard heating load Standard outside temp. (Heating) Building adaptation Standard outside temp. (Cooling) Max. cooling down (outside temperature ref.)
Page 71
"Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Excessive temperature in the heating buffer Stored energy Excessive temperature in the hot water buffer Internal pump Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment...
Page 72
REMKO Smart-Control Touch "Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment Time program A Time program B...
Page 73
"Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment Time program A Time program B Time program C Time program function Room temperature reduction Room temperature increase...
Page 74
REMKO Smart-Control Touch "Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment Time program A Time program B...
Page 75
"Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment Time program A Time program B Time program C Time program function Room temperature reduction Room temperature increase...
Page 76
REMKO Smart-Control Touch Unmixed & mixed circuit switching times Designation Factory setting Customer system Time program A Mo-Su 00:00-24:00 Time program B Mo-Fr 05:00-23:00 Sa-Su 06:00-23:00 Time program C Mo-Fr 05:00-23:00 Sa-Su 06:00-23:00 "Settings" menu item (continued) - Expert Level 2 menu item...
Page 77
Level 2 menu item Level 3 menu item Level 4 menu item Number of power tariffs Time field Tariff 1-9 Power tariff 1-9 Graduated tariff Continuous hot water influence Short-term hot water influence Short-term heating influence Continuous heating influence PV personal use variant Power tariff 1 Feed-in tariff Heat pump...
Page 78
REMKO Smart-Control Touch "Settings" menu item (continued) - Expert Level 2 menu item Level 3 menu item Level 4 menu item Operating mode Response to disable signal S16 Min. pump speed A 43 (%) Auxiliary heat generator Max. pump speed A 43 (%)
Page 79
"Settings" menu item (continued) - Expert Manual mode - actuator relay test With this menu item, you can control the individual actuators (pumps, mixing valves, etc.) manually or specify values of probes for checking. Parameter Selection parameter Manual mode Permanent / Deactivated / 15 minutes Solar cycle pump A 01 Auto / On / Off...
Page 80
REMKO Smart-Control Touch "Settings" menu item (continued) - Expert Manual mode - actuator relay test (continued) Parameter Selection parameter Pump indoor unit (top - HP 1) Auto / On / Off Speed (HP 1) 10 % - 100 % A43.2...
Page 81
"Settings" menu item (continued) - Expert Manual mode - probes (continued) Parameter Selection parameter Storage tank temperature, upper Probe value / stipulated value Temperature -60°C - 250°C Storage tank temperature, centre Probe value / stipulated value Temperature -60°C - 250°C Outside temperature Probe value / stipulated value Temperature...
Page 82
REMKO Smart-Control Touch "Settings" menu item (continued) - Expert Manual mode - probes (continued) Parameter Selection parameter S14.2 Probe value / stipulated value 4th mixed heating cycle return temp. S14.2 -60°C - 250°C Temperature Heat generator return temperature (HP 1)
Page 83
"Settings" menu item (continued) - Expert Commissioning Information on the "Commissioning" menu item is described in the separate "Commissioning wizard" chapter on the next pages. "Settings" menu item (continued) - Expert Chimney sweep Level 2 menu item Level 3 menu item Mode Normal operation/test mode Hot water valve...
REMKO Smart-Control Touch 5.2 Commissioning wizard When starting the controller for the first time the commissioning assistant is started in order to implement the basic programming of the existing system. After commissioning has been fully completed, the default set of parameters is enabled.
Page 85
Setting the language All menu entries, commands and parameters are displayed in plain language in the language selected. Menu item Parameter Factory setting Deutsch English Francais Italiano Language setting Espanol Deutsch Portugues Nederlands Polski Čeština Setting the time zone for the winter time Selecting the time zone for the winter time allows the switch to daylight savings time to occur automatically.
Page 86
REMKO Smart-Control Touch Setting the time From here, you can set the current time. The controller has automatic summertime switching, which can also be activated from the menu "Language/Time” (+1 CET). When setting the time, first the hours are selected, and then the minutes.
Page 87
Operating mode Two operating modes are available: Bivalent alternative Monoenergetic Menu item Parameter Factory setting Monoenergetic Operating mode selection Monoenergetic Bivalent alternative Selection of the auxiliary heat generator: - Bivalent alternative (heat pump or oil/gas-fired boiler or wall heating) - Monoenergetic (heat pump and/or Smart Serv electric heating element) according to usable limits The operating mode of the internal pump in the indoor unit must be defined here in the level “Expert "...
Page 88
Circulation type (dependent on which probes are used) Impulse circulation: (Only in conjunction with the REMKO impulse generator) If briefly dispensing water triggers an impulse on the flow-operated safety device, this is registered by the controller and the circulation pump is started up. This means that the circulation is also active when it is required.
Page 89
The descriptions of the 1st and 2nd mixed heating cycle are identical to the unmixed heating cycle. The mixed heating cycles each require a supply and return probe! These probes are included in the scope of supply of the mixed REMKO heating cycle groups.
Page 90
REMKO Smart-Control Touch System separation underfloor heating Activation if a mixed heating cycle is separated by a heat exchanger. If system separation is activated, the set temperature is increased. Menu item Parameter Factory setting Deactivated System separation FBH Deactivated Activated...
Page 91
Setting the standard heating load The standard heating load is obtained by multiplying the specific heating load by the living area to be heated. You can calculate the standard heating load from the following table. This method is only estimated and should be set to the values defined by an expert. Building performance requirements Year of construction Specific heating load...
Page 92
REMKO Smart-Control Touch Solar speed control system Activate the solar speed regulation if you want the solar cycle pump to modulate according to solar capacity. Activation of the speed control system for the pump in the solar cycle. the pump can be activated according to demand, for efficiency reasons;...
Page 93
Menu item Parameter Factory setting Solar set temperature 5 °C - 95 °C 85 °C REMKO recommends installing a domestic hot water mixer with solar hot water preparation. WARNING! Implement measures on site to ensure sufficient scalding protection!
Page 94
REMKO Smart-Control Touch Heat carrier medium Selection of the filled solar liquid for calculation of the amount of solar heat. Menu item Parameter Factory setting Water DOWCAL 10 DOWCAL 20 TYFCOR TYFOCOR-L TYFOCOR-LS ANTIFROGEN-N Heat carrier medium ANTIFROGEN-SOL TYFOCOR-L Temper-10...
Hot water tank capacity. ¯ The precondition for the dynamic hygiene function is that a REMKO flow sensor (e.g. EDP no. Hygiene function 254070) has been installed. The dynamic hygiene function can be individually adjusted to the user ¯...
Page 96
The definitive bivalency point for your system can be found in the Smart-Control Touch con- 2nd heat generator troller instructions in the expert level under "Settings/ Heat pump".
For this purpose, implement the changes with the grey slide controls as described in the chapter "Setting the heating/cooling operating mode". The REMKO Smart-Control Touch controller can control max. one unmixed and four mixed heating cycles!
We recommend adapting plant-specific parameters, such a heating limits and bivalence point, to the design data! You can find further hydraulics examples at www.remko.de Hydraulic circuit diagram Functions: Heating and hot water incl. Smart-Serv emergency heating coil Fig. 53: Example hydraulic diagram...
Page 99
Basic settings for the hydraulic diagram Menu item Parameter Factory setting Country Deutschland - Slovensko Germany Load setting Accept the parameters Saving process Language Deutsch - Polski Deutsch Time zone Var. time zones possible Winter + 1(CET) Date Year/Month/Day Basic settings Time Hours/Minutes Basic settings...
Page 100
REMKO Smart-Control Touch Menu item Parameter Factory setting Base point/standard inlet temperature/ Cooling curve adjustment Deactivated standard outside temperature 2nd mixed heating cycle Activated/Deactivated Deactivated Operating mode Heating/cooling Heating and cooling Deactivated Heating cycle mode Heating curve Deactivated Heating curve adjustment...
Error messages on the Smart Control Operating messages, warnings and error display on the Smart-Control Operating messages Description Desig. Details Storage tank 1: Max. The temperature on one of the probes in storage tank 1 is ID6000 temperature reached higher than the maximum permitted storage tank temperature ID6001 HW request There is an active requirement to charge the storage tank Heat pump compressor...
Page 102
REMKO Smart-Control Touch Description Desig. Details Low pressure differ- ID6115 The pressure difference is too low to start the compressor ence Maximum defrosting ID6116 Maximum defrosting period period Heat pump compressor ID6122 Heat pump compressor stop stop Error Description Desig. Details The anti-freeze protection in the heat pump's heat exchanger was triggered due to an inlet temperature that is too low.
Page 103
Description Desig. Details ID7072 Inverter malfunction HP 1 Inverter malfunction ID7073 DLT probe fault HP 1 Temperature probe DLT was not detected ID7074 Fan malfunction HP 2 Fan malfunction ID7075 Low pressure HP 2 Pressure transducer P1 Overheating point ID7076 HP 2 Temperature below overheating point for too long undershot...
Page 104
REMKO Smart-Control Touch Description Desig. Details Communication mal- ID7109 HP 1 1st heat pump function µPC ID7150 EEV motor fault EEV motor fault. Please contact an authorised service techni- cian Communication mal- ID7170 HP 2 2nd heat pump function Open contact - storage...
Page 106
REMKO Smart-Control Touch Description Desig. Details The medium flow rate fell below the heat pump's minimum medium flow rate due to defrosting or in cooling mode. After ID7251 Min. medium flow rate eliminating the cause of the error, the indoor and outdoor units...
Page 107
Description Desig. Details ID7278 Low overheating The compressor is disabled due to overheating being too low. Open contact - internal ID7283 Open contact - internal return temperature probe return temp. probe Short circuit - internal ID7284 return temperature Short circuit - internal return temperature probe probe Low suction gas The compressor is disabled due to the suction gas tempera-...
Page 109
Description Desig. Details Short circuit - 2nd ID7329 mixed heating cycle Short circuit - 2nd mixed heating cycle inlet temp. inlet temp. The anti-freeze protection in the heat pump's heat exchanger was triggered due to an inlet temperature that is too low. After µPC ID7332 Anti-freeze protection eliminating the cause of the error, the controller must be...
Page 110
REMKO Smart-Control Touch Description Desig. Details The temperature has currently dropped below the guar- Lower application area ID8139 anteed application area of the external unit in heating (heating) mode Upper application area The guaranteed application area of the external unit in...