Installation

1. Cautions of Installation

Please use the product with installed on the panel due to the danger of the electric shock.
Do not install the product in the places below.
• Place where a person unconsciously touches the terminal
• Place with strong vibration, impact or electromagnetic field
• Place with exposed to the abrasive or flammable gases
• Place with rapid temperature change or much moisture, dust or salt
• Place with exposed to the direct sunlight or excessively high or low temperature
• Place with materials easy to be caught by the fire
The case and the front part of the product are made from the plastic (PC) and equipped with
insulators but do not directly install the product on the material with easily burnt.
Do not place the equipment or wiring which causes the noise near from the product. In particular,
sufficiently preheat the product when used at low temperature below 0°C. Also, do not put the
equipment with severe heat near from the product.
Turn all the gauges off and do the wiring.
The product operates under 100 - 240 V AC / 50 - 60 ㎐ without additional operation. Do not use
the power other than the ratings. This may cause the electric shock or the fire.
Do not operate the product with wet hand. This may cause the electric shock.
Please follow the existing notice to reduce the danger of the fire, electric shock or damages in use.
Please refer to how to install for the ground. (Ground resistor: Less than 100 Ω)
Install the product in a place with sufficient ventilation and do not cover the vent hole of the product.
The overvoltage protection is included in the categoryⅡ (IEC 60664-1) and the use environment is
the Pollution DegreeⅡ.
Do not use a sharp tool or apply too much power on the touch screen.

2. Installation method

Please cut off the power provided to the product before the installation. Take care
not to touch the terminal due to the danger of the electric shock under the power
application.
Danger
Use the steel plate with the thickness of 2 ~ 5 ㎜ for the panel.
Slide the product into the panel from the front side of the panel.
Hook the dedicated clamp to the hole on the product and fix it with bolts (Place first with slightly
tightening each clamp and then fix).