(3) List of switch settings
System remote controller (SF44SRA)
Name
System controller master/slave
setting changeover
External input function changeover
Operation prohibit setting changeover
Operation prohibit range setting changeover
* Valid only when SW3-4 is ON
Not used
Not used
Schedule timer (YT34STA)
Name
System controller master/slave
setting changeover
External input function changeover
Operation prohibit setting changeover
Operation prohibit range setting changeover
* Valid only when SW3-4 is ON
Set temperature display changeover
Not used
Not used
ON/OFF remote controller (YT40ANRA)
Name
System controller master/slave
setting changeover
External input function changeover
Switch NO.
Function
OFF
Master SC setting
SW3-1
ON
Slave SC setting
No.
SW3
External input signal function
2
3
1
OFF
OFF
Do not use external inputs
SW3-2, 3
2
OFF
ON
Change between emergency stop/normal
3
ON
OFF
Set ON/OFF
4
ON
ON
Set ON/OFF, prohibit/enable
Set the local remote controller operation prohibit functions
SW3-4
OFF
Operation prohibit use disable To not use this system's operation prohibit function
ON
Operation prohibit enable
Set the range to control the operation prohibit functions used with this system.
SW3-5
OFF
Only local remote controller To prohibit operation of only the local remote controller
ON
Including system controller
SW3-7
SW3-8
Switch NO.
Function
OFF
Master SC setting
SW3-1
ON
Slave SC setting
No.
SW3
External input signal function
2
3
Do not use external inputs
1
OFF
OFF
SW3-2, 3
Change between Emergency stop/Normal
2
OFF
ON
3
ON
OFF
Set ON/OFF
4
ON
ON
Set ON/OFF, prohibit/permit
Set the local remote controller operation prohibit functions
SW3-4
Operation prohibit use disable To not use this system's operation prohibit function
OFF
ON
Operation prohibit enable
Set the range to control the operation prohibit functions used with this system.
Only local remote controller To prohibit operation of only the local remote controller
SW3-5
OFF
ON
Including system controller
OFF
Celsius display
SW3-6
ON
Fahrenheit display
SW3-7
SW3-8
Switch NO.
Function
OFF
Master SC setting
SW4-1
ON
Slave SC setting
No.
SW4
External input signal function
2
3
1
OFF
OFF
Do not use external inputs
SW4-2, 3
2
OFF
ON
Change between Emergency stop/Normal
3
ON
OFF
Set ON/OFF
4
ON
ON
Set ON/OFF, prohibit/permit
Setting method
To set system controller as master
To set system controller as slave
Input state
Level input
Level input
Pulse input (0.5sec or more)
To use this system's operation prohibit function
To prohibit operation of the local remote controller
and other system controllers
Setting method
To set system controller as master
To set system controller as slave
Input state
Level input
Level input
Pulse input (0.5sec or more)
To use this system's operation prohibit function
To prohibit operation of the local remote controller
and other system controllers
To display set temperature as Celsius (;)
To display set temperature as Fahrenheit (,)
Setting method
To set system controller as master
To set system controller as slave
Input state
Level input
Level input
Pulse input (0.5sec or more)
Default
setting
OFF
OFF
OFF
OFF
OFF
OFF
Default
setting
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Default
setting
OFF
OFF
$

Hide quick links: