uilding Air Conditioning Control System
System Remote Controller
PAC-SF44SRA
Schedule Timer
PAC-YT34STA
ON/OFF Remote Controller
PAC-YT40ANRA
Installation Manual
This manual describes only the installation of the System Controller, capable of managing and controlling air conditioners, and LOSSNAY. Refer to
the installation manuals enclosed with the air conditioner for details on wiring and installing the air conditioner unit.
Safety Precautions
To ensure safety, always read
below before starting installation.
1 Safety Precautions
• The following two symbols are used to denote dangers that may be caused by incorrect use and their degree:
his symbol denotes what could lead to serious injury or death if you misuse above remote controllers.
WARNING
his symbol denotes what could lead to a personal injury or damage to your property if you misuse above remote controllers.
CAUTION
• After reading this installation manual, keep it in a place where the final user can see it anytime he or she wants to it.
When someone moves, repairs or uses above remote controllers, make sure that this manual is forwarded to the final user.
Ask your dealer or technical representative to install the unit.
Any deficiency caused by your own installation may result in an electric
shock or fire.
Install in a place which is strong enough to withstand the weight
of above remote controllers.
Any lack of strength may cause above remote controllers to fall down,
resulting in personal injury.
Firmly connect the wiring using the specified cables. Carefully
check that the cables do not exert any force on the terminals.
Improper wiring connections may produce heat and possibly a fire.
Never modify or repair above remote controllers.
Any deficiency caused by your modification or repair may result in an
electric shock or fire.
Consult with your dealer about repairs.
Do not install in any place exposed to flammable gas leakage.
Flammable gases accumulated around the body of above remote
controllers may cause an explosion.
Do not use in any special environment.
sing in any place exposed to oil (including machine oil), steam and
sulfuric gas may deteriorate the performance significantly or give
damage to the component parts.
When installing the remote controller in a hospital or communication facility, take ample countermeasures against noise.
Inverters, emergency power supply generators, high-frequency medical equipment, and wireless communication equipment can cause the remote
controller to malfunction or to fail. Radiation from the remote controller may effect communication equipment and prevent medical operations on
the human body or interfere with image transmission and cause noise.
Wire so that it does not receive any tension.
Tension may cause wire breakage, heating or fire.
Completely seal the wire lead-in port with putty.
Any dew, moisture, insects entering the unit may cause an electric
shock or a malfunction.
Do not wash with water.
Doing so may cause an electric shock or a malfunction.
Do not install in any place at a temperature of more than 40
;
less than 0
or exposed to direct sunlight.
Doing so may cause deformation or a malfunction.
Do not install in any steamy place such a bathroom or kitchen.
Avoid any place where moisture is condensed into dew. Doing so may
cause an electric shock or a malfunction.
2 Confirming the Supplied Parts
Confirm that the box includes the following parts, in addition to this installation manual:
(1) Remote controller (Body, lower case) ........................................................
(2) Cable for external input (5 wire) .................................................................
(3) Cable for external output (4 wire)...............................................................
(4) Cross recessed pan head screw (M4 × 30) ...............................................
(5) Wood screw (4.1 × 16, used for directly hooking to the wall).....................
(6) Room name label or room name record sheet...........................................
(7) Operation Manual.......................................................................................
he remote control cord is not supplied with the product.
NOTE:
Prepare electrical wiring that conforms to the specifications given below.
Electrical wiring specification (CVVS)
Use 1.25mm
cable for any extension that exceeds 10m.
2
¥ 10m or shorter
: 0.75mm
two-wire cable
2
¥ Longer than 10m : 1.25mm
two-wire cable
2
3 System Configurations
(Refer to the "System Design and Work Manual" for the outdoor unit for details.)
entral management
transmission line
Indoor and
Outdoor unit
outdoor transmission line
Interlocked operation
with ventilation unit
(1) When connecting to a central management transmission line
A power supply unit (PAC-SC34KUA) is required.
Number of connected system controllers
ower supply unit
ON/OFF remote controller
AC-SC34KUA
1 to 5 units
* The power consumption of the system controller, schedule timer and group remote controller is half of the ON/OFF remote
controller. Thus, interpret the power consumption per unit as half of the ON/OFF remote controller.
Leave as is
SW2-1[ON]
CN41
ON
OFF
[051]
1
2 3 4 5 6 7 8 9 10
[001]
TB7
TB3
* Outdoor unit
: SW position
[101]
Leave as is
Group 1
SW2-1[ON]
CN41
ON
OFF
[052]
1
2 3 4 5 6 7 8 9 10
TB7
TB3
ON/OFF
System
Schedule timer
remote controller
remote controller
PAC-YT34STA
PAC-YT40ANRA
PAC-SF44SRA
[201]
[202]
[203]
* Number of units that can be supplied with power supply unit (For above system)
Power supply unit
Model: PAC-SC34KUA
1×1/2
One system remote controller
WARNING
Ensure that installation work is done correctly following this
installation manual.
Any deficiency caused by installation may result in an electric shock or
fire.
All electrical work must be performed by a licensed technician,
according to local regulations and the instructions given in this
manual.
Any lack of electric circuit or any deficiency caused by installation may
result in an electric shock or fire.
Do not move and re-install above remote controllers yourself.
Any deficiency caused by installation may result in an electric shock or
fire.
Ask your distributor or special vendor for moving and installation.
CAUTION
Do not install in any place where acidic or alkaline solution or
special spray are often used.
Doing so may cause an electric shock or malfunction.
Use standard wires in compliance with the current capacity.
A failure to this may result in an electric leakage, heating or fire.
Do not touch any PCB (Printed Circuit Board) with your hands or
with tools. Do not allow dust to collect on the PCB.
Doing so may cause fire or an electric shock.
Do not remove the insulation sheet on the PCB.
Doing so may cause an electric shock.
Do not touch any control button with your wet hands.
Doing so may cause an electric shock or a malfunction.
;
or
Do not press any control button using a sharp object.
Doing so may cause an electric shock or a malfunction.
Never apply 100VAC or 200VAC. The maximum voltage that can
be applied on this unit is 30VDC.
Applying an excessive voltage may cause damage, igniting or fires.
1
1
1
2
emote
controller
2
lower case
1
1
Remote controller wiring entry points can support electrical
wiring of maximum 1.25mm
.
2
However 0.75mm
electrical wiring is recommended for use.
2
LOSSNAY
(independent/
Indoor unit
M-NET remote controller
interlocked)
System remote controller
schedule timer
group remote controller
1 to 10 units
[002]
[003]
[004]
[009]
[102]
[103]
Group 2
Group 3
[005]
[006]
[007]
[105]
[106]
[107]
Group 4
Group 5
Group 6
+
1×1/2
+
1×1
One schedule timer
One ON/OFF remote controller
(2) When connecting to indoor and outdoor transmission line
Up to three system controllers can be connected to the M-NET transmission line's indoor and outdoor transmission line.
A power supply unit is not required in this case, but the short-circuit connector of one of the connected outdoor units must be
connected to CN40.
hen the system remote controller is connected to the indoor and outdoor transmission line, the number of indoor units
NOTE :
that can be connected in that refrigerant system will be reduced by two.
CAUTION
Interchange
short-circuit
connector from
CN40
ON
CN41 to CN40.
OFF
[051]
TB7
TB3
Leave as is
CN41
ON
OFF
[052]
TB7
TB3
ON/OFF
remote controller
PAC-YT40ANRA
[201]
(3) Setting the various M-NET addresses
The need for address settings and the address setting range will differ according to the system configuration. (The address can-
not be set in duplicate).
System controller
ON/OFF remote controller
System remote controller
Schedule timer
(4) Setting the system controller address
emote controller main unit
(5) When using with master system controller
When connecting multiple system controllers, the system controller with many functions is designated as the "master", and the
system controllers with few functions are designated as the "slaves". The "master/slave" functions of the system controller used
together are as follows.
The functions have a priority in order of G50A (MJ-103MTRA) > PAC-SF44SRA > PAC-YT34STA > PAC-YT40ANRA > PAC-SC30GRA > LMAP02-E.
System remote controller (44SRA)/Schedule timer (34STA)
Master side
Slave side
* The switch is set to "Master" as the factory setting.
4 Using the External Input and Output
When using the external input and output functions, use the external input and output cables provided with the remote controller.
emote
(5 wire cable for input and 4 wire cable for output are provided.)
controller
body
1. External signal input function
(1) External Input
Emergency stop/Normal, ON/OFF and Prohibit/Permit local remote controller operation control can be applied to all units
being controlled by inputting the no-voltage contact signal from an external source.
No.
1
Do not use external input
Change between Emergency stop/Normal.
All units will stop with the external input,and all operations of this unit,other system controllers and
2
local remote controller will be prohibited.
Set ON/OFF
All units will turn ON/OFF according to the input state. ON/OFF operations using this unit and the
3
local remote controller will be prohibited when using this function.
Set ON/OFF and Prohibit/Permit.
All units are started or stopped, or all local remote controller operations are prohibited according to
4
the input state. When prohibit is input, the local remote controller's ON/OFF, operation mode, set
temperature and filter reset operations will be prohibited. Operation with this system will be enabled.
NOTE :
For System remote controller and Schedule timer
* If the SW3-4 "operation prohibit setting changeover" is set to "OFF (disable)", use is possible only for emergency stop.
* If the SW3-5 "operation prohibit range setting changeover" is set to "ON (including system controller), operations of the local remote
controller and other system controllers will be prohibited by the prohibit input. If set to "OFF (only local remote controller)", operation
of only the local remote controller will be prohibited. (When the level "emergency stop" or "ON/OFF" is input, operation of the other
system controllers will also be prohibited regardless of the switch setting.)
For ON/OFF remote controller
* All units are stopped when emergency stop is input, and ON/OFF operations of this unit, other system controllers and local remote
controller will be prohibited.
* Only ON/OFF of the local remote controller will be prohibited with the prohibit input.
(2) Level signal and pulse signal
(A) Level signal
Contact ON
Contact OFF
OFF
Contact ON
Contact OFF
Normal
(3) External input specification
N2
Lead wires (5 wires)
No. 1
Green
No. 2
Yellow
No. 3
Orange
No. 4
Red
No. 5
Brown
(4) Example of a recommended circuit
A) Level signal cases
Remote controller
[008]
main unit
The relays and extension cables, etc. must be prepared separately at the site.
Use a no-voltage contact and minute load relay (minimum application load 5VDC-1mA).
The length of the connection cable extension should not exceed 10m. (Use a cable of 0.3mm
Cut of the cable not being used close the connector and properly insulate the cut off ends with tape or the like.
[108]
NOTE :
For level signal
Group 7
Contact operation
OFF
ON
=
2 (unit)
For pulse signal
* Operation will continue even if a ON signal is input during operation. (This also applies to OFF, prohibit and enable).
* If the local remote controller is prohibited, ON/OFF, operation mode, temperature and filter reset operations using the local
remote controller will be prohibited. (Only ON/OFF are prohibited for the ON/OFF remote controller.)
* Set the pulse duration (contact ON time) to 0.5sec or more.
hen connecting the system controller to the indoor and outdoor transmission line, operations from the
system controller will be disabled if the outdoor unit's power is turned OFF, etc.
SW2-1[ON]
1
2 3 4 5 6 7 8 9 10
[001]
[002]
* Outdoor unit
: SW position
[101]
[102]
Group 1
Group 2
SW2-1[ON]
1
2 3 4 5 6 7 8 9 10
[005]
System
[105]
Schedule Timer
Remote Controller
PAC-YT34STA
PAC-SF44SRA
Group 4
[202]
[203]
Address setting range
Setting method
201 to 250
Set to the minimum group No. to be controlled + "200"
201 to 250
Random within address range shown on left
201 to 250
Random within address range shown on left
hen setting the address, prepare a precision screwdriver
[( ), 2.0mm (w)], and keep the applied load to less than
otary switch
19.6N.
CAUTION
SW 2
SW 1
Setting with other methods could damage the rotary switch.
¥ The address No. that can be set on the remote controller is
NOTE :
within the range of 201-250.
10
1
The 100 digit is fixed at "2".
Example: Address of 201
¥ If an address other than those listed above is set, an address
setting error occurs and "AdE" is displayed.
SW3-1: OFF
SW3-1: ON
External input signal functions
(B) Pulse signal
(Example) Case of ON/OFF signal
Signal 1 (ON)
ON
OFF
Signal 2 (OFF)
Emergency
STOP
Normal
* The same applies to Prohibit/Permit.
Level signal for Emergency stop/Normal
Level signal for ON/OFF
Emergency stop/Normal input
ON/OFF input
Not used
Not used
Not used
Not used
Not used
Not used
ommon 0V
B) Pulse signal cases
CN2
CN2
1
green
green
yellow
ON/OFF or
orange
Emergency stop
red
brown
brown
Maximum 10m
Maximum 10m
Remote controller
main unit
External input
Operation state
Emergency stop/Normal
ON/OFF
ON
Normal
Emergency stop
OFF
ON
OFF
Emergency stop
Normal
ON
OFF
[003]
[004]
[009]
[103]
Group 3
[006]
[007]
[008]
[106]
[107]
[108]
Group 5
Group 6
Group 7
Default address setting
201
201
202
ON/OFF remote controller (40ANRA)
SW4-1: OFF
SW4-1: ON
System remote
ON/OFF remote
Schedule timer
controller
controller
SW3
SW3
SW4
Input state
2
3
2
3
2
3
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
Level input
ON
OFF
ON
OFF
ON
OFF
Level input
Pulse input
ON
ON
ON
ON
ON
ON
(0.5sec or more)
0.5sec or more
Contact ON
Contact OFF
0.5sec or more
Contact ON
Contact OFF
OFF
ON
OFF
Pulse signal for ON/OFF, Prohibit/Permit
On input
Off input
Prohibit local remote controller operation input
Permit local remote controller operation input
X1
ON
X2
OFF
Y1
Prohibit
Y2
Permit
2
or thicker.)

Advertisement

loading

Summary of Contents for Mitsubishi Electric PAC-SF44SR

  • Page 1 (2) When connecting to indoor and outdoor transmission line Up to three system controllers can be connected to the M-NET transmission line's indoor and outdoor transmission line. A power supply unit is not required in this case, but the short-circuit connector of one of the connected outdoor units must be uilding Air Conditioning Control System connected to CN40.
  • Page 2 2. External signal output function xtra space around 6 How To Install remote controller (1) External output xternal size of remote controller In the case when one or more air conditioner units are "ON", and an error is occurring on one or more air conditioner units, (1) Choose a location in which to install the system remote controller (electric a signal indicating that an error is occurring is output.