Entelli-Switch 250 Microprocessor Controller - ABB Zenith ZTSCT Series Operation And Maintenance Manual

Closed transition and bypass isolation closed transition automatic transfer switches, 100-4000 a
Table of Contents

Advertisement

Entelli-Switch 250 Controller
Entelli-Switch 250 Controller
Consists of two major assemblies:
The Microprocessor contains the following:
I.
A.
Entelli-Switch 250 Board - Customer Input and
Output (I/O) for system interface. Located on the
left hand side of the back of the unit (see figure 7)
1.
I/O accessories that can be found here are:
a.
Engine start relay P output
b.
Pre-Signal to transfer T3, W3 and
UMD output (optional)
c.
Transfer Inhibit Q3 and Q7 input
(optional)
d.
Remote test Q2 input (optional)
e.
Network interface ZNET
input/output (optional)
B.
LCD and Keypad located on the exterior of the
door (see figure 8)
1.
User accessibility to the following:
a.
LED indication of source availability
b.
LED indication of transfer switch position
c.
LCD screen indicates:
(1) timer count down (numeric)
(2) event reporting (text)
d.
Keypad provides user interface to:
[in conjunction with LCD screen]
(1) Setting sensors and timers
(2) Configuring logic accessories
II. The Controls Power Supply (CPS)
Contains transformers which drop line voltage
to control level for controller input and SCR
inputs (see figure 7).
6
I/O Interface
ZTSCT / ZBTSCT Operation & Maintenance Manual
Engine Start Relay P
Figure 7
S 1 O K
2 1 : 5 6
M O N 2 3 A P R 2 0 0 8
M O R E
T E S T
Figure 8
Entelli-Switch 250
Board
Battery Strip
and
Access
Code Label
CPS
ABB Zenith