How To Set The System Clock - ABB Zenith ZTSCT Series Operation And Maintenance Manual

Closed transition and bypass isolation closed transition automatic transfer switches, 100-4000 a
Table of Contents

Advertisement

Accessory Definitions
UMD
Universal Motor Load Disconnect Circuit: Auxiliary
Contact opens 0-60 seconds prior to transfer in either
direction, re-closes after transfer. Can be configured by
end user for Pre-transfer, Post-transfer, or both.
VI
Voltage Imbalance (Three Phase)
For a three phase source, this feature monitors phase
voltage ratios based on a selected range within a selected
time window. Should any phase fall below the selected
lower window limit or exceed the selected higher window
limit within the selected time frame, the controller initiates
transfer to the other source.
Range: 5% to 20% of Nominal voltage,
10 to 30 seconds window, user adjustable.
Resolution: 1% Increments
Minimum Differential: 2% between "Fail"
and "Restore" settings.
Factory default: 10% "Fail", 8% "Restore", 30 Seconds.
See CFG Menu page 17 to configure ON or OFF.
See SET Menu page 18 to set Percentage and time windows

How to Set the System Clock

How to Set the System Clock
Set System Clock, time and date
·
If the clock is not set, the display will show SET SYSTEM
CLOCK on the second line of the S1 OK screen.
·
The S1 OK screen will show time (hours and minutes)
on the second line if the system clock has been set.
(Date on third line)
Setting the System Clock
(Start from S1 OK screen)
1. Remove battery protective white plastic strip
near P relay. *
2. Press MORE then press SET.
3. Press MORE and scroll to SET SYSTEM CLOCK
using the MORE key.
4. Press SEL.
5. ENTER ACCESS CODE located on the white label
on the back of the controller.
6. Press SEL.
7. Use the up and down keys to change the hour value.
8. Press SAVE (this will enter this value and move
cursor to minutes).
9. Use the up and down keys to change the minutes.
10. Press SAVE (this will enter this value and move
cursor to month).
ABB Zenith
(cont'd)
W
Time Delay (S2) Source 2 Stable Timer. To delay transfer
to Source 2. Adjustable 0-5 minutes in 1 second increments.
Standard setting is 1 second. Adjust via SET menu (see
page 18)
YEN
Bypass Timers Key utilizing Keypad. When applicable,
the system prompts the user to press a button to bypass
(T) or (W) Timers should the user so desires.
ZNET
Network Communications Interface Card
11. Use the up and down key up to change the month.
12. Press SAVE (This will enter this value and complete
the clock setting).
13. Use the up and down keys to change the date.
14. Press SAVE (this will enter this value and move
cursor to year).
15. Use the up and down keys to change year.
16. Press SAVE (this will enter this value and
compete the clock setting).
17. To edit settings, press SEL and repeat steps 6-16.
18. If the setting is satisfactory, press MORE (unit then
returns to the SET menu then press BACK, then ESC)
*
Replacement battery part #K-4100
Battery will last 5 years and provides power to retain clock
function only (Controller functions without battery).
ZTSCT / ZBTSCT Operation & Maintenance Manual
13