Electrical Requirements - Wickes Aquatronic 4 Ultra Installation And Operating Instructions Manual

Electric shower
Table of Contents

Advertisement

ELECTRICAL REQUIREMENTS

WARNING!
W-006-A
THIS APPLIANCE MUST BE EARTHED
The installation, supply cable and circuit
protection must conform with BS 7671 (IEE
wiring regulations) and be sufficient for the
amperage required.
The following notes are for guidance only:
1
The shower must only be connected to a
230-240V ac supply. If you are installing a
shower with a kilowatt rating above 9kW, it
is advisable to contact the local electricity
supply company.
1.1 The electrical rating of the shower is shown
on the rating label (Fig.3) within the unit.
2
Before making any sort of electrical
connection within the installation make sure
that no terminal is live. If in any doubt,
switch off the whole installation at the mains
supply and remove the correct fuse.
3
The shower must be connected to its own
independent electrical circuit. IT MUST NOT
be connected to a ring main, spur, socket
outlet, lighting circuit or cooker circuit.
3.1 The electrical supply must be adequate for
the loading of the unit and existing circuits.
4
Check your consumer unit (main fuse box)
Fig.
Schematic of installation circuit
has a main switch rating of 80A or above
and that it has a spare fuse way which will
take the fuse or Miniature Circuit Breaker
(MCB) necessary for the shower (Fig.4).
4.1 If your consumer unit has a rating below
80A or if there is no spare fuse way, then the
RCD
(can be part of
installation will not be straightforward and
consumer unit)
may require a new consumer unit serving
the house or just the shower.
4.2 You will need to contact the local electricity
company. They will check the supply and
carry out what is necessary.
Consumer
Fuse or
unit
MCB
5
For close circuit protection DO NOT use a
rewireable fuse. Instead use a suitably rated
80A or 100A
Miniature Circuit Breaker (MCB) or cartridge
main switch
fuse (see Table A).
Meter
5.1 A 30mA residual current device (RCD) must
tails
be installed in all UK electric and pumped
shower circuits. This may be part of the
consumer unit or a separate unit.
6
A 45 amp double pole isolating switch with
Aquatronic 4 Ultra electric shower
Shepperton Park,
Triton Road, Nuneaton,
Warwickshire, CV11 4NR
Fig.
Pull cord
isolating switch
Shower
unit
Meter
Incoming
supply
fuse
shower with a kilowatt rating above 9kW, it
is advisable to contact the local electricity
supply company.
1.1 The electrical rating of the shower is shown
on the rating label (Fig.3) within the unit.
2
Before making any sort of electrical
connection within the installation make sure
that no terminal is live. If in any doubt,
switch off the whole installation at the mains
supply and remove the correct fuse.
3
The shower must be connected to its own
independent electrical circuit. IT MUST NOT
be connected to a ring main, spur, socket
outlet, lighting circuit or cooker circuit.
3.1 The electrical supply must be adequate for
the loading of the unit and existing circuits.
4
Check your consumer unit (main fuse box)
has a main switch rating of 80A or above
and that it has a spare fuse way which will
take the fuse or Miniature Circuit Breaker
(MCB) necessary for the shower (Fig.4).
4.1 If your consumer unit has a rating below
80A or if there is no spare fuse way, then the
installation will not be straightforward and
may require a new consumer unit serving
the house or just the shower.
4.2 You will need to contact the local electricity
company. They will check the supply and
carry out what is necessary.
5
For close circuit protection DO NOT use a
rewireable fuse. Instead use a suitably rated
Miniature Circuit Breaker (MCB) or cartridge
fuse (see Table A).
5.1 A 30mA residual current device (RCD) must
be installed in all UK electric and pumped
shower circuits. This may be part of the
consumer unit or a separate unit.
6
A 45 amp double pole isolating switch with
a minimum contact gap of 3 mm in both
poles must be incorporated in the circuit.
CIRCUIT PROTECTION
6.1 It must have a mechanical indicator showing
unit
when the switch is in the OFF position, and
rating
the wiring must be connected to the switch
without the use of a plug or socket outlet.
7.0kW
6.2 The switch must be accessible and clearly
7.5kW
identifiable, but out of reach of a person
8.0kW
using a fixed bath or shower, except for the
8.5kW
cord of a cord operated switch, and should
9.0kW
be placed so that it is not possible to touch
9.5kW
the switch body while standing in a bath or
E-002-A
shower cubicle. It should be readily
10.5kW
accessible to switch off after using the
shower.

7
Where shower cubicles are located in any
rooms other than bathrooms, all socket
Table A
cartridge
MCB
fuse
30/32A
30A
32A
35A
40A
35A
40A
45A
40A
45A
40/45A
45A
45A
45A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents