1 Extended and Advanced Cascade Controller
Option
Connect the control cables and relief the cables by the enclosed cable strips.
Various systems must not be mixed.
1
Fit the extended cradle and terminal cover.
Replace the LCP
Connect power to the frequency converter.
Wiring the Terminals
Do not combine low voltage parts and PELV systems.

1.3.2 Advanced Cascade Controller MCO 102

The MCO 102 option supports a maximum of 8 pumps and is able to alternate the lead pump with 2 frequency converter relays per pump. This reduces
the need for external auxiliary switches as well as cost of installation.
When MCO 102 (C-option) is used, the number of relays can be increased to a total of 13 by adding the MCB 105 (B-option).
NB!
Before start, interrupt the power supply to the frequency converter. Never install an option card into the frequency converter during
operation.
Electrical Data:
Max terminal load (AC)
Max terminal load (DC)
Min terminal load (DC)
Max switching rate at rated load/min load
8
®
MI.38.C3.02 - VLT
is a registered Danfoss trademark
®
VLT
Operating Instructions
240 V AC 2A
24 V DC 1 A
5 V 10 mA
6 min
-1
/20 sec
-1