Electrical Installation As Interface - EBRO ARMATUREN EP 501 B Quick Start Manual

Electropneumatic positioner
Table of Contents

Advertisement

Available languages

Available languages

10.4 Electrical installation AS interface
10.4.1 E lectrical connection with circular plug-in
connector M12 x 1, 4-pole
Views of plugs
The views show the image from the front looking at the pins. the solder
connections are behind them.
Pin 4:
NC
Pin 1:
Bus +
Fig. 14: Bus connection without external supply voltage
Pin 4:
24 V +
Pin 1:
Bus +
Fig. 15: Bus connection with external supply voltage (optional)
Bus connection without external / with external supply voltage
24
Pin 3:
Bus –
Pin 2:
NC
Pin 3:
Bus –
Pin 2:
GND
english
Type EP 501 B
Electricalconnection
Pin
Designation
Configuration
1
Bus +
AS Interface bus line +
NC or GND
not used or external supply
2
(optional)
voltage – (optional)
3
Bus –
AS Interface bus line –
NC or 24 V +
not used or external supply
4
(optional)
voltage + (optional)
Tab. 17: Pin assignment of circular plug-in connector for AS-Interface
When the operating voltage is applied, the positioner is operating.
Actuate the automatic adjustment of the positioner, as described
in the chapter entitled "11.2 Specifying the basic settings".
10.4.2 Programming data
Profile version S-7.3.4
I/O con-
7 hex
figuration
ID code
3 hex (analog profile)
Extended
F hex (default value, can
ID code 1
be changed by the user)
Extended
4 hex
ID code 2
Profile
S-7.3.4
Tab. 18: Programming data
Profile version S-7.A.5
7 hex
A hex
7 hex
5 hex
S-7.A.5

Advertisement

Table of Contents
loading

Table of Contents