National Instruments SCC-CI20 User Manual
National Instruments SCC-CI20 User Manual

National Instruments SCC-CI20 User Manual

Current input module
Hide thumbs Also See for SCC-CI20:

Advertisement

Quick Links

USER GUIDE
SCC-CI20 Current Input Module
USER GUIDESCC-CI20 Current Input Module
Conventions
<>
»
bold
The SCC-CI20 converts current to voltage by passing it through a precision
249 Ω resistor and sending the resulting voltage to the E Series DAQ device
as a 0 to +5 V signal. The SCC-CI20 accepts up to two current sources at a
maximum of 20 mA. A differential instrumentation amplifier buffers each
input signal.
The following conventions are used in this guide:
Angle brackets that contain numbers separated by an ellipsis represent
a range of values associated with a bit or signal name—for example,
P1.<3..0>.
The » symbol leads you through nested menu items and dialog box options
to a final action. The sequence File»Page Setup»Options directs you to
pull down the File menu, select the Page Setup item, and select Options
from the last dialog box.
This icon denotes a note, which alerts you to important information.
This icon denotes a caution, which advises you of precautions to take to
avoid injury, data loss, or a system crash. When this symbol is marked on
the product, refer to the Read Me First: Safety and Radio-Frequency
Interference document, shipped with the product, for precautions to take.
When symbol is marked on a product, it denotes a warning advising you to
take precautions to avoid electrical shock.
When symbol is marked on a product, it denotes a component that may be
hot. Touching this component may result in bodily injury.
Bold text denotes items that you must select in software, such as menu
items and dialog box options. Bold text also denotes parameter names.

Advertisement

Table of Contents
loading

Summary of Contents for National Instruments SCC-CI20

  • Page 1 249 Ω resistor and sending the resulting voltage to the E Series DAQ device as a 0 to +5 V signal. The SCC-CI20 accepts up to two current sources at a maximum of 20 mA. A differential instrumentation amplifier buffers each input signal.
  • Page 2: What You Need To Get Started

    SC-2345 refers to both the SC-2345 connector block and configurable connector. SCC refers to any SCC Series signal conditioning module. What You Need to Get Started To set up and use the SCC-CI20, you need the following items: ❑ SC-2345/2350 with one of the following: –...
  • Page 3: Device Specific Information

    J(X+1), where X is 0 to 7, and connect the input signals to the module as described in the Connecting the Input Signals section. If you use the SCC-CI20 in a dual-stage configuration, you must use it as the first stage. Plug the SCC-CI20 into any socket J(X+9) and plug the second-stage SCC into socket J(X+1), where X is 0 to 7.
  • Page 4 X. The value of X is determined by the number of the SC-2345 socket, J(X+1) or J(X+9), where you plug in the SCC-CI20. Figure 1 shows the SCC-CI20 signal connections. SCC-C120 E Series DAQ Device Signal Source Overvoltage Protection AI (X ) –...
  • Page 5 Input Resistor for AI (X+8) 3 Assembly Number Figure 2. SCC-CI20 Parts Locator Diagram For information about how to configure the SCC-CI20 module using NI-DAQmx, refer to the SCC Quick Start Guide. Using the SC-C120 when Scaling Voltage Measurements If you configured the SCC-CI20 using Measurement & Automation...
  • Page 6: Specifications

    Offset error ..........±0.6 mV max Temperature stability of offset error..±21 µV/°C max Dynamic Response Bandwidth (–3 dB, amplitude ≤4 mA) ...10 kHz Output slew rate........0.75 V/µs min Temperature range is 23 °C ± 5 °C. SCC-CI20 Current Input Module User Guide ni.com...
  • Page 7: Power Requirement

    Operating temperature......0 to 50 °C Storage temperature ....... –20 to 70 °C Humidity ..........10 to 90% RH, noncondensing Maximum altitude ........2,000 m Pollution Degree (indoor use only) ..2 © National Instruments Corporation SCC-CI20 Current Input Module User Guide...
  • Page 8: Electromagnetic Compatibility

    Safety The SCC-CI20 is designed to meet the requirements of the following standards of safety for electrical equipment for measurement, control, and laboratory use: • IEC 61010-1, EN 61010-1 • UL 3111-1, UL 61010B-01 • CAN/CSA C22.2 No. 1010.1 For UL and other safety certifications, refer to the product label, or visit...
  • Page 9 AI (X+8). A GND is the reference for the ±15V supplies. AI GND and A GND connect to the SC-2345 at the SCC-PWR connector. Pins 17 to 20 accept signals from a first-stage module if you are cascading two modules. Table 1. SCC-CI20 Pin Signal Assignments Pin Number Signal...
  • Page 10 *371068B-01* Corporation. Product and company names mentioned herein are trademarks or trade names of their respective companies. For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software, the patents.txt file on your CD, or ni.com/patents.