Johnson Controls M9106-AG 2N0 Series Installation Instructions Manual

Electric non-spring return actuators

Advertisement

Quick Links

Installation
IMPORTANT: Use this M9106-AGx-2N0x Series
Actuator only to control equipment
under normal operating conditions.
Where failure or malfunction of the
actuators could lead to personal
injury or property damage to the
controlled equipment or other
property, additional precautions must
be designed into the control system.
Incorporate and maintain other
devices, such as supervisory or alarm
systems or safety or limit controls,
intended to warn of or protect against
failure or malfunction of the
actuators.
IMPORTANT : Utiliser ce M9106-AGx-2N0x Series
Actuator uniquement pour
commander des équipements dans
des conditions normales de
fonctionnement. Lorsqu'une
défaillance ou un dysfonctionnement
du actuators risque de provoquer des
blessures ou d'endommager
l'équipement contrôlé ou un autre
équipement, la conception du
système de contrôle doit intégrer des
dispositifs de protection
supplémentaires. Veiller dans ce cas
à intégrer de façon permanente
d'autres dispositifs, tels que des
systèmes de supervision ou d'alarme,
ou des dispositifs de sécurité ou de
limitation, ayant une fonction
d'avertissement ou de protection en
cas de défaillance ou de
dysfonctionnement du actuators.
The actuator may be mounted in any convenient
orientation. When installing the DPT-2015 Differential
Pressure Transmitter on the actuator, mount it so the
tubing connecting the flow pick-up device to the
DPT-2015 creates a moisture trap. This will prevent
condensation from entering the sensor.
No extra mounting brackets, linkage, or couplers are
required for standard mounting, but wiring terminals
must be accessible and protected from moisture and
corrosive fumes.
© 2014 Johnson Controls, Inc.
Part No. 34-636-1077, Rev. B
M9106-AGx-2N0x Series Electric
Non-Spring Return Actuators
Installation Instructions M9106AGx-2N0x
Parts Included
M9106-AGx-2N0x Actuator
CBL-2000-1 Wiring Harness and DPT-2015-0
Differential Pressure Transmitter (included with the
M9106-AGS-2N02)
No. 10 self-drilling sheet metal screw
Special Tools Needed
5/16 in. (8 mm) square socket
3/8 in. (10 mm) 12-point socket
drill with a 5/16 in. hex nut driver
digital voltmeter (for troubleshooting the
transmitter)
Mounting
To mount the actuator to a damper:
1. Position the actuator on the damper shaft so the
damper shaft protrudes through the actuator
coupler as shown in Figure 1.
Figure 1: Mounting on the Damper Shaft
2. Make sure the actuator is in the desired mounting
position, parallel to the mounting surface as shown
in Figure 2.
Issue Date June 3, 2014
Damper
Damper
Shaft
www.johnsoncontrols.com
1

Advertisement

loading

Summary of Contents for Johnson Controls M9106-AG 2N0 Series

  • Page 1 No extra mounting brackets, linkage, or couplers are required for standard mounting, but wiring terminals must be accessible and protected from moisture and corrosive fumes. © 2014 Johnson Controls, Inc. Part No. 34-636-1077, Rev. B www.johnsoncontrols.com...
  • Page 2 Approximately an 1/8 in. (3.2 mm) Gap Figure 4: Damper Position Icons Mounting Surface To set the actuator stroke, proceed as follows: DPT-2015 1. Grasp the damper shaft firmly with pliers and rotate the damper fully closed. (See Figure 5.) Gear Damper Release...
  • Page 3 90° IMPORTANT: Do not remove the end-stop 60° set screws, as this could interfere with the actuator’s 30° End-stop operation. 45° 10° Set Screws on End Stops (2 each) 4. Hand tighten the set screw so it remains in this Coupler Set position.
  • Page 4: Setup And Adjustments

    The plenum-rated 20 in. (0.5 m) CBL-2000-2 and Wiring 72 in. (1.8 m) CBL-2000-3 Wiring Harnesses are also available. (See Table 1.) CAUTION: Risk of Electric Shock. Setup and Adjustments Disconnect the power supply before making electrical connections to avoid electric shock. Air Pressure (M9106-AGS-2N02) MISE EN GARDE : Risque de décharge The flow pickup device provided with the Variable Air...
  • Page 5: Troubleshooting

    2. Set up and zero using HVAC PRO software one complete cycle open and closed. when using a DPT-2015 with a Johnson Controls VAV Series controller. Refer to the Variable Air DPT-2015 Volume Controller Technical Bulletin (LIT-6363040) for details.
  • Page 6: Technical Data

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.