Description of the acyclic WRITE service in accordance with DP V1
The acyclic write service always derives the slot and index from
the hexadecimal 16-bit variable index for reading. - Four
parameters are handed over in the request telegram:
Request telegram:
Parameter
Value range
name
Slot
0 - 254
Index
0 - 254
Length
1 - 240
Data
......
Table 4
Positive response telegram:
Parameter
Value range
name
Length
1 - 240
Table 5
16 Operation
Data type
Description
Byte
Slot for addressing the
variable to write.
Byte
Index for addressing the
variable to write.
Byte
Number of bytes to write-
Bytes
Bytes for value of variable to
write. It is impossible to
specify more bytes than
defined by length.-
Data type
Description
Byte
Number of written bytes. If
the required length for the
data is inferior than the
requested length, the
negative value is entered
here. If the required length for
the data is superior to the
requested length, the
requested length is entered
here. --
Negative response telegram:
Parameter
Value range
name
Error
......
ID
Error code 1
......
Error code 2
......
Table 6
Data type
Description
Byte
Provides information about
the sending protocol system
(here PROFIBUS-DP V1).-
The only valid value that may
appear here is 128.-
Byte
Error details. ID: -
0xA1
Variable defined by
slot and index is
unknown.-
0xA8
Controller firmware
does not support
PROFIBUS-DP
V1.-
0xB0
Service not yet
usable.-
0xC0
Too many requests
at the same time.
Current request will
not be processed. -
-
Byte
Not used