Description of the acyclic READ service in accordance with DP V1
The acyclic READ service hands over 3 parameters: -
Request telegram:
Parameter
Value range
name
Slot
0 - 254
Index
0 - 254
Length
1 - 240
Table 1
Positive response telegram:
Parameter
Value range
name
Length
1 - 240
Data
......
Table 2
Data type
Description
Byte
Slot for addressing the
variable to read
Byte
Index for addressing the
variable to read
Byte
Number of bytes to read
Data type
Description
Byte
Number of read bytes. If the
required length for the data is
inferior to the length in the
request, the smaller value is
entered here. If the required
length for the data is superior
to the length in the request,
the value of the request is
entered here. ---
Byte
Bytes for required size. The
number of bytes corresponds
exactly to the specified
length. -
Negative response telegram:
Parameter
Value range
name
Error
......
ID
Error code 1
......
Error code 2
......
Table 3
Data type
Description
Byte
Provides information about
the sending protocol system
(here PROFIBUS-DP V1). -
The only valid value that may
appear here is 128.-
Byte
Error details. ID:-
0xA0
Variable defined by
slot and index is
unknown. -
0xA8
Controller firmware
does not support
PROFIBUS-DP
V1.-
0xB0
Service not yet
usable.-
0xC0
Too many requests
at the same time.
Current request will
not be processed. -
-
Byte
Not used
Operation 15