Corridors

In corridors with a maximum width of 3 m the distance
between two smoke alarm devices may not exceed 15 m.
Keep a distance of less than 7.5 m between the smoke
alarm and the front surface of the corridor. One smoke
alarm has to be installed in each of intersection, junction
and corner areas of corridors.
5.2.7

Platforms and galleries

If the height of a room is divided by a platform or gallery
with an area greater than 16 m² as well as a length and
width of 2 m, a smoke alarm has to be installed below
these constructions.
5.3

Mounting the smoke alarm

Following careful selection of the installation location,
the ceiling bracket has to be mounted first.
You can mount the smoke alarm to the ceiling using two
screws and plugs.
If you have already taught-in the smoke alarm to
other devices, please remove the ceiling bracket
first by unlocking the release lever. Turn the
smoke alarm anticlockwise and pull it from the
ceiling bracket.