Flat Ceilings - HomeMatic HmIP-SWSD Mounting Instruction And Operating Manual

Smoke alarm with q label
Table of Contents

Advertisement

Available languages

Available languages

Start-up
transformers or halogen lamp cable systems, as
well as fluorescent lamps or energy-saving lamps
and in particular to its ballasts (minimum distance
50 cm)
garages (exhaust emissions)
dusty and dirty rooms (measuring chamber gets
dirty quickly or false alarms are triggered)
in the vicinity of windows, ventilators, fans or any
other locations where the air moves around a lot
in the vicinity of areas where people smoke
in the vicinity of solid steel beams, large metal
surfaces, etc. as they could significantly inhibit the
transmission or receipt of the wireless signal. Mov-
ing the alarm by just a few centimetres can often
help.
5.2.4

Flat ceilings

The smoke alarm must be mounted on the ceiling in the
centre of a room. Keep a minimum distance of 50 cm to
the walls and corners of the room to avoid a build-up of
air that stops the rising smoke.
If rooms are separated by joists (divisions) into ceiling
panels with a hight greater that 20 cm, one smoke alarm
per ceiling surface has to be installed if the area is greater
than 36 m².
48

Advertisement

Chapters

Table of Contents
loading

Table of Contents