Carrier 48LC 04 Controls, Start-Up, Operation And Troubleshooting page 72

Single package rooftop units with comfortlink controls version 1.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

APPENDIX — LOCAL DISPLAY AND CCN TABLES
ITEM
EXPANSION
COOL
Cooling Configuration
N.STG
Number of Stages
MRT.C
Compressor Min On Time
MOT.C
Compressor Min Off Time
RST.C
Runtime to Reset Strikes
C.DEC
Cool Stage Decrease Time
C.INC
Cool Stage Increase Time
FOD.C
Fan--- off Delay, Mech Cool
FTT
Fan Transition Time
ALM.N
Alert Each Strike
CA.LO
Circuit A Lockout Temp
LA.SP
Low Ambient ODF
Setpoint
D.CMP
Diagnose Comp Safety
MX.SA
Max Suction Change CirA
CS.A1
Current Sensing A1
DHUM
Dehum Control Type
SAT
Supply Air Temperature
SA.PD
SAT Cool Demand (+)
Level
SA.ND
SAT Cool Demand (--- )
Level
SAT.U
Minimum SAT Upper Level
SAT.L
Minimum SAT Lower Level
SPT
Space Temperature
CL.PD
SPT Cool Demand (+)
Level
CL.ND
SPT Cool Demand (--- )
Level
C.LAG
Cool Thermal Lag Factor
SST
Low Suction Control
SST.O
Suction OK Temperature
SST.1
Low Suction --- Level 1
SST.2
Low Suction --- Level 2
SST.3
Low Suction --- Level 3
CK.DL
Delay On Low SST Check
FLSU
Fan Low Suction Temp
HEAT
Heating Configuration
HT.TY
Type of Heat Installed
N.HTR
Number of Heat Stages
MRT.H
Heat Minimum On Time
MOT.H
Heat Minimum Off Time
H.DEC
Heat Stage Decrease Time
H.INC
Heat Stage Increase Time
FOD.E
Fan--- off Delay, Elect Heat
FOD.G
Fan--- off Delay, Gas Heat
HT.LO
Heating Lockout Temp
SAT
SAT.H
SAT Heat Mode Sensing
SAM.L
Maximum SAT Lower Level
SAM.U
Maximum SAT Upper Level
SPT
Space Temperature
HT.PD
SPT Heat Demand (+)
Level
HT.ND
SPT Heat Demand (--- )
Level
H.LAG
Heat Thermal Lag Factor
ECON
Economizer Configuration
EC.EN
Economizer Installed
E.CTL
Economizer Control Type
MP .25
Econ Min at 25% Fanspeed
MODE — CONFIGURATION (cont)
RANGE
UNITS
1 to 2
2
120 to 999
sec
180
300 to 999
sec
300
120 to 999
sec
300
120 to 999
sec
300
120 to 999
sec
450
0 to 600
sec
75
60 to 600
sec
75
No/Yes
sec
480
0 to 100F
° F
0
0 to 80
° F
40
No/Yes
Yes
0 to 100
PSIG
4
Disable/Enable
Disable
0=No Control
0
1=Max Dehum
2=Max Comfort
0.5 to 10
^F
1
--- 10 to --- 0.5
^F
--- 1
35.0 to 65.0
° F
52
35.0 to 65.0
° F
40
0.5 to 5
^F
1
--- 5 to --- 0.5
^F
--- 1
0 to 5
1
10 to 50
° F
18
10 to 50
° F
20
5 to 50
° F
15
0 to 50
° F
10
0 to 300
sec
0
28 to 50
° F
32
0=No Heat
0 (50 series with no electric heat)
1=Gas
1 (48 series)
2=Electric
2 (50 series with electric heat)
1 to 2
2 (all except below)
1 (48 series Low Nox or single
phase unit))
1 (50 series with low or medium
heat)
1 (50 series 04---05 with high heat)
60 to 999
sec
120
60 to 999
sec
120
120 to 999
sec
300
120 to 999
sec
450
10 to 600
sec
30
45 to 600
sec
45
40 to 125
° F
75
Disable/Enable
Disable
85 to 200
° F
140
85 to 200
° F
160
0.5 to 5
^F
1
--- 5 to --- 0.5
^F
--- 1
0 to 5
1
No/Yes
No: no FIOP
Yes: FIOP
1=Dig/Position
1
2=Dig/Command
3=Analog Ctrl
0 to 100
%
0
72
CCN TABLE/
DEFAULT
Sub--- TABLE
COOL_CFG
HEAT_CFG
ECON_CFG
PAGE
CCN POINT
NO.
11
NUM_STAG
MIN_ON
16
MIN_OFF
16
MIN_ON_S
26
STAGEDEC
16
STAGEINC
16
COOL_FOD
15
FANTRANT
17
ALM_NOW
27
OATLCMPA
16
LAODF_SP
17
DIAGCOMP
27
MAXDSSPA
27
A1_SENSE
28
DEHUMCTL
17
SAT_POS
SAT_NEG
SATMIN_H
16
SATMIN_L
16
DEM_POS
DEM_NEG
COOL_LAG
SSTOK
29
SSTLEV1
28
SSTLEV2
28
SSTLEV3
28
SSTCKDLY
FANLOSUC
17
HEATTYPE
18
NUM_HEAT
19
HMIN_ON
19
HMIN_OFF
19
HSTAGDEC
19
HSTAGINC
19
ELEC_FOD
15
GAS_FOD
15
OATLHEAT
18
SAT_HEAT
18
SATMAX_L
18
SATMAX_H
18
HDEM_POS
HDEM_NEG
HEAT_LAG
ECONO
19
ECON_CTL
21
MINP_25
22