Ccn Tables - Carrier 48LC 04 Controls, Start-Up, Operation And Troubleshooting

Single package rooftop units with comfortlink controls version 1.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

APPENDIX — LOCAL DISPLAY AND CCN TABLES
ITEM
RUN STATUS
VIEW
Auto View of Run Status
HVAC
HVAC Mode Status
OCC
Currently Occupied
SAT
Supply Air Temperature
ALRM
Current Alarms & Alerts
TIME
Time of Day
VERS
Software Version Numbers
MBB
CESR131505--- xx--- xx
ECB
CESR131249--- xx--- xx
MARQ
CESR131171--- xx--- xx
VFD1
FW Version --- xxxxx
NAVI
CESR131227--- xx--- xx
MODE
Control Modes
SYS
Current System Mode
HVAC
Current HVAC Mode
F. MOD
Indoor Fan Mode
HV.DN
Remote HVAC Mode Disable
EFF.C
Cool Setpoint In Effect
EFF.H
Heat Setpoint In Effect
OCC
Currently Occupied
T.OVR
Timed Override in Effect
LINK
Linkage Active
D.LMT
Demand Limit In Effect
C.LOC
Compressor OAT Lockout
H.LOC
Heat OAT Lockout
OK.EC
OK to Use Economizer?
COOL
Cooling Status
DMD.C
Cooling Demand
AVL.C
Available Cooling Stages
REQ.C
Requested Cooling Stages
MAX.C
Max Allowed Cool Stages
LMT.C
Max Cool Stage In Effect
F.SPD
Commanded Fan Speed
CMP .A
Circuit A Compressor
TG.A
Timeguard A
LDR.A
Circuit A Loader
TG.L
Timeguard Loader
SST.A
Sat. Suction Temp A
SSP .A
Suction Pressure A
SCT.A
Sat. Condenser Temp A
SCP .A
Condenser Pressure A
HEAT
Heating Status
DMD.H
Heating Demand
AVL.H
Available Heating Stages
REQ.H
Requested Heating Stages
MAX.H
Max Allowed Heat Stages
LMT.H
Max Heat Stage In Effect
F.SPD
Commanded Fan Speed
HT.1
Heat Stage 1 Relay
TG.H1
Heat Stage 1 Timeguard
HT.2
Heat Stage 2 Relay
TG.H2
Heat Stage 2 Timeguard
ECON
Economizer Status
EC.CP
Econo Commanded Position
EC.AP
Econo Actual Position
EC.MP
Min Position in Effect
IAQ.S
IAQ Level (switch)
IAQ
IAQ Level (sensor)
OAT
Outdoor Air Temperature
RAT
Return Air Temperature
ENTH
Outdoor Enthalpy Switch
OAQ
OAQ Level (sensor)
PE.1
Power Exhaust 1 Relay
PE.2
Power Exhaust 2 Relay
MODE — RUN STATUS
EXPANSION
RANGE
1=Disabled
2=Ventilation
3=Cool
4=Heat
No/Yes
xxx..x
xx
xx.xx
(xx--- xx in table)
1=Disabled
2=Run Enabled
3: Service Test
1=Disabled
2=Ventilation
3=Cool
4=Heat
x
No/Yes
xx.x
xx.x
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
xxx.x
x
x
x
x
xxx
Off/On
xxx
Off/On
xxx
xxx.x
xxx.x
xxx.x
xxx.x
xxx.x
x
x
x
x
xxx
Off/On
xxx
Off/On
xxx
xxx
xxx
xxx
Low/High
xxxx
xxx.x
xxx.x
Low/High
xxxx
Off/On
Off/On
CCN TABLE/
UNITS
Sub--- TABLE
STATUS DISPLAY
(VIEW = Display only)
° F
hh.mm
VERSIONS
MODEDISP
° F
° F
COOLDISP
^F
%
sec
sec
° F
psig
° F
psig
HEATDISP
^F
%
sec
sec
ECONDISP
%
%
%
° F
° F
66
CCN WRITE
CCN POINT
STATUS
HVACMODE
OCCUPIED
SAT_DISP
ALRMALRT
TIMECOPY
MODEL_NUMBER_01
MODEL_NUMBER_02
MODEL_NUMBER_03
VFD1_SW
MODEDISP
SYS_MODE
HVACMODE
IDF_MODE
HVACDOWN
forcible
CSP_EFF
HSP_EFF
OCCUPIED
forcible
MODETOVR
MODELINK
MODEDMDL
COMPLOCK
HEATLOCK
ECONCOOL
COOL_DMD
AVLCSTGS
REQCSTGS
MAXCSTGS
forcible
CSTGLIMT
FANSPEED
COMP_A
TIMGD_A
LOADER
TIMGD_L
SST_A
SSP_A
SCT_A
SCP_A
HEAT_DMD
AVLHSTGS
REQHSTGS
MAXHSTGS
forcible
HSTGLIMT
FANSPEED
HEAT_1
TIMGD_H1
HEAT_2
TIMGD_H2
ECONOCMD
ECONOPOS
MIN_POS
forcible
IAQIN
IAQ
OA_TEMP
RETURN_T
ENTHALPY
OAQ
PE_1
PE_2