Identification
Supply voltage
Range P
Output signal
PB/MWP
SUPPLY
OUTPUT
+SUPPLY
-COMMON
Electrical connection
Type no. (Indicates transmitter specification - see key below)
Type no.
MBS 4201-
MBS 4251-
MBS 4701-
MBS 4751-
Measuring range
0 –
1 bar ..................
0 – 1.6 bar ..................
0 – 2.5 bar ..................
0 –
4 bar ..................
0 –
6 bar ..................
0 – 10 bar ..................
0 – 16 bar ..................
0 – 25 bar ..................
0 – 40 bar ..................
0 – 60 bar ..................
0 – 100 bar ..................
0 – 160 bar ..................
0 – 250 bar ..................
0 – 400 bar ..................
0 – 600 bar ..................
Max. 600 bar ..................
2 | 520B7682 | IC.PI.P20.C7.02
6430 Nordborg
Denmark
:
0...10 bar
e
0...1 Mpa
:
2 MPa/20 bar
:
10...28 V d.c.
:
4...20 mA
:
PIN 1
:
PIN 2
1
–
10
12
14
16
1 ...........
18
3 ...........
20
7 ...........
22
4 ...........
24
5 ...........
26
C ...........
28
D ...........
30
32
34
36
38
1 .............................
XX
1 ........................................
2 ........................................
PRESSURE TRANSMITTER
MBS 4701-2011-1AB08
060G4307
0539
II 1G
DEMKO 01 ATEX 127938X
Ex ia IIC T4 Ga
IECEx ULD 12.0005X
Ui
:
28V
For :
Ii
: 100 mA
Ambient
Pi
:
0,7 W
temperature
Li
:
8 µH
See:
:
user instruction
Ci
50 nF
Pressure connection
G B 0 4 .........
DIN 3852-E-G1/4, Gasket: DIN 3869-14-NBR
A B 0 8
.........
G1/2A (EN 837)
A C 0 4 .........
1/4-18 NPT
A C 0 8 .........
1/2-14 NPT
....
F A 0 8
.....
ISO 6149-2, M14x1.5 -6g, O-ring 11.3x2.2, NBR
....
D A 0 5 .....
M10 x 1 female with flange connection
) Only MBS 4201 and MBS 4251
1
Electrical connection
Plug, DIN 43650, Pg9
2 m cable
)
1
Plug, DIN 72585-A1-3.2-Sn
5 m PVC cable
)
1
10 m PVC cable
)
1
6 m ETFE cable
)
1
12 m ETFE cable
)
1
) Only MBS 4201 and MBS 4251
1
Output signal
4 – 20 mA
Pressure reference
Gauge
Absolute
Code number
111 = WWY
Production - week/year
(WW/Y)
02803 = Serial no.
)
1
© Danfoss | DCS (im) | 2017.07
Need help?
Do you have a question about the MBS 4201 and is the answer not in the manual?