4.4 Set value limits
Lubrication cycle can be set within 1 min - 999 h 59 min. In grease lubrication channels,
pumping is started twice during one lubrication cycle. In oil lubrication channels pumping is
started once during one lubrication cycle.
Maximum pressurization time can be set within 0 s - 9999 s. The channel can be closed by
entering 0 s for maximum pressurization time, in which case lubrication is not performed.
In pressure transmitter channels the pressure high limit can be set within 0 - 160 bar. The
pressure low limit can be set between 0 bar and the set pressure high limit.
4.5 Configuration display
Channel configuration settings are displayed by selecting Page - Othr - Conf at the basic
display.
CH2 SG2 Machine 1
Group 1 Pump CH12
Relay
Chnl
Figure 11.
Display lines
Note
The first line indicates the selected channel
•
number (CH2)
•
operation mode (SG2)
•
name (Machine 1)
The second line indicates the selected channel
•
group (Group 1)
•
pump control channel (Pump CH2)
The third line indicates the selected channel
•
the operation mode for channel-specific alarm relay (Relay 0)
•
pressure control unit type (P-transm.)
The fourth line indicates
•
the function key texts
13401BEN.doc
0
P-transm.
---- Set
Configuration display
The texts in brackets are sample display texts.
SAFEGREASE, SAFEOIL, MULTILUBE
ST-1340
Esc
16 (19)
27.12.2004 Rev. 1B