Material Data; Environmental Declarations; Working And Test Pressure; Water Quality - Lindab Plexus Series Installation Instructions Manual

Active chilled beam
Hide thumbs Also See for Plexus Series:
Table of Contents

Advertisement

l in d a b | w e s i m p l i fy c ons t ru c t ion
Installation instructions

3.4 Material data

Type
Dry weight, kg
Water content, cooling, l
Water content, heating, l
Water content, cooling only, l
Copper pipes, quality

3.5 Environmental Declarations

Please visit
www.lindqst.com
• Select Documentation Finder
• Select "Plexus"
• Select "Related Documents"
declaration
or
Declaration of conformity.

3.6 Working and test pressure

Lindab's waterborne products have been manufactured
and tested according to Pressure Equipment Directive
97/237EC. The products are classified as SEP - Sound
Engineering Practice.
Pressure table
Pressure class
Max. working pressure
Max. recommended dynamic pressure
Max. test pressure
10
Plexus I 60
Cooling/Heating
Cooling/Heating
11.6
1.0
0.2
1.2
EN 12735-2
CU-DHP
Building product
PN10
10 bar
0.2 bar
16 bar
We reserve the right to make changes
2019-06-20
Plexus I 120
Plexus F 60
Cooling/Heating
18.6
20
17.2
1.3
1.0
0.4
0.2
1.3
1.2
EN 12735-2
EN 12735-2
CU-DHP
CU-DHP

3.7 Water quality

Lindab recommend water treatment and quality to be
according to VDI 2035-2.
• The water preparation and maintenance for the chilled
beam water circuit must be handled by a specialist.
• To prevent corrosion, the water circuit must be
airtight.
• The water system must also be equipped with
aerators to remove any build-up air in the system.
• The water must be oxygen free, to prevent corrosion.
• The water system must be filled with potable water
that complies with the "EC directive 98/83/EC".
• pH value of water must be between approximately
6-9 pH.
• The water velocities should not exceed 1m/s, and
should be kept as close to the nominal flow as
possible to minimize noise and optimize the energy
yield.
• Use in-line strainers to remove dirt particles from the
water.
• If the water contains any additive inhibitor, then it
must be appropriate to use with copper and solder.

3.8 Air quality

Primary supply air have to be clean, dry and filtered
before reaching the beam.

3.9 Capacity test

Lindabs active chilled beams are Eurovent-certified and
tested according to EN-15116.
Please visit
Plexus
on
www.lindqst.com
Eurovent
for more details.
Plexus
Plexus F 120
Cooling/Heating
28.9
30.3
1.3
0.4
1.3
EN 12735-2
CU-DHP
and see