Commissioning
Connection Design C to external housing
Fig. 5-14 Connection Design C to external housing Ex-Zone I
Design C: Electrically connect the pilot burner
Fig. 5-15 Connect pilot burner version C
High voltage on the bare ignition electrode!
Pilot burner is only permitted to be operated with correct earthing.
In the event of damage to the earthing insulation, the device should be shut down; further
DANGER!
With version C in particular there is a danger of death when removing or omitting the earth-
ing, the housing earthing must be connected directly to the ignition transformer earthing!
operation without repair is not permitted.
40
Connect the pilot burner
cables as follows
No.
Wire colour
1
bl
2
bl
Neutral conductor
3
bl
Ignition transformer N
4
bl
Ignition transformer L
5
bl
6
bl
PE
gn/ye
Protective conductor
Function
Phase
-N
TR
-L
TR
COM
NO