3
Product Description
Connection: Air
Air quality
Air ratio
Flow rate (air quantity)
NOTICE
At temperatures in the combustion chamber of over 500°C (932 °F), if the pilot burner is off, a
cooling air supply of 50% of the max. combustion air should be provided.
Free of dust, oil, grease and aerosols
The quality for the compressed air supply should conform to
ISO 8573-1:2010 class ( 7 : 4 : 4 ). Non-observance can
result in short-circuits due to material deposits in the housing.
0.3...0.5 (the remaining air quantity must be provided by the
combustion chamber)
GFI48: max. 50 m
GFI70: max. 150 m
GFI89: max. 250 m
25
3
3
/h (65.39 yd
/h)
3
3
/h (196.19 yd
/h)
3
3
/h (326.98 yd
/h)