4 . F A U L T S , E R R O R S A N D T R O U B L E S H O O T I N G; Description Of Fault Messages And Their Causes - BPC DUPLEX 250 Easy Use, Maintenance And Installation Manual

Table of Contents

Advertisement

4 . F a u l t s , e r r o r s a n d t r o u b l e s h o o t i n g

Description of fault messages and their causes

4.1.
Fault
The equipment
cannot be started
The equipment is
not supplying
enough air
The equipment is
not heating or is
heating
insufficiently
Water is dripping
from the
equipment
Description
The equipment
Power supply is not connected
remains idle even
after the required
performance level
Not found
was selected
The equipment is
Blocked filter
providing a
significantly lower
volume of air
A mechanical obstacle at fresh
air suction or supply air outlets
Not found
When the heater
The electric heater is not
has been started,
connected to power supply
supply air
continues to be
cold
Response of the electric
heater's heat protection
Low maximum capacity of the
heater
Not found
Water droplets
The condensate drain siphon is
form between the
insufficiently flooded
door and body of
the equipment
The condensate drain is blocked
during operation
with dirt
The seal groove is damaged
(the fault can be accompanied
by a whistling sound caused by
air flowing through the gap)
Water droplets
The condensate drain seal or
form at the
line is damaged
condensate drain
connection point
Not found
Possible cause
13
Troubleshooting
Connect the equipment to power
supply (switch on upstream
safety circuit breakers)
Disconnect from power
supply and contact a service
technician
Disconnect the equipment
from power supply
Replace the filter cloth or
cassette
If the equipment has been in
operation for more than approx.
4 years, clean the heat recovery
exchanger/s
Check whether the suction
openings of fresh air or supply
air outlets are not mechanically
covered
Remove any obstacles
Visually and by listening check
whether the dampers open
properly
Disconnect from power
supply and contact a service
technician
Connect the equipment to power
supply (switch on upstream
safety circuit breakers) – can
only be done by an authorized
person
Wait to see if the fault does not
sort itself out after approx. 1
hour
Does not constitute a fault
(insufficient capacity designed)
Disconnect from power
supply and contact a service
technician
Disconnect the equipment
from power supply and flood
the condensate drain siphon
Disconnect the equipment
from power supply and clean
the condensate drain including
the siphon
Disconnect the equipment
from power supply and replace
the seal
Disconnect the equipment
from power supply and re-seal
the condensate drain
Disconnect from power
supply and contact a service
technician