Cleaning The Plastic Heat Recovery Exchanger - BPC DUPLEX 250 Easy Use, Maintenance And Installation Manual

Table of Contents

Advertisement

When replacing filters, do not remove the unit's door – use the special cover for filter replacing.
Sliding the filter frame out of the unit and replacing the cloth
Release the filter plugs in the
housing unit using the product in
the package
– pull straight on
Remove the cover on the
unit's enclosure
-start from the bigger recess
Properly fitted cloth – the blue /
red side faces the unit's ports
and the white one the heat
recovery exchanger

Cleaning the plastic heat recovery exchanger

3.3.
The recommended interval of heat recovery exchanger cleaning is about 2 years, depending on the nature of the operating
environment.
If necessary, wash the heat recovery exchanger block with warm water with a detergent several times; the water temperature
should be up to 60 °C, ideally such that you could keep your hands in it comfortably (e.g. BODE Kohrsolin FF ).
Do not expose the heat recovery exchanger to ultraviolet light and sunlight, store it in a dark place if necessary.
ATTENTION: Never use cleaning agents that might contain organic solvent to clean the heat recovery exchanger as they
could cause its irreversible damage!
Do not pull on a slant!
Take out the frame with filter cloth
Fitting filter covers
-proceed from one side to another
Slide a new filter cloth onto the frame
- the fibre is to be slid onto the
Press the cover into the unit's enclosure so
that it is flush with the lid's edge along the
entire perimeter
11