M-bus web server

Advertisement

Use
The M-bus web server reads devices connected directly to the web server, devices
connected to the web server via level converters as well as devices connected to the web
server via RF converters.
Web server can be used:
Alone with up to 20 directly connected, wired M-bus devices
As a master on an M-bus network with up to six connected level converters, each with up
to 60 M-bus devices and/or
As a master on an M-bus network with up to 23 RF converters, each with up to 500 RF
devices
The web server can read out up to 2,500 wireless devices and up to 250 wired devices. It
records the data from the connected M-bus devices, can evaluate the data, and sends email
notifications on events and alarms.
The device storage can save data for a period of max. 10 years (data is read once a day).
A PC/Internet browser reads the data and log files either locally over Ethernet or from
anywhere over the Internet. In addition, the report files can be periodically transmitted with
device data to an email recipient or to an FTP server.
NOTICE
Forgotten password
In the event a password for web server access via an Internet browser is lost, it can no
longer be reset or requested. The web server must be replaced.
An email can be sent on events and alarms.
The web server can be integrated in the Synco IC-Cloud. This permits the periodic upload of
invoicing and trend data as well as alarm messages to the cloud per customized settings as
well as distributing the information to the corresponding customers via email.
The web server has three digital inputs and two digital outputs. The change of state to inputs
or outputs are recorded in the event log and/or per email depending on the configuration.
Both outputs can be manually switched via web operation.
Web server is protected against short circuits and surges.
2
Siemens
Building Technologies
A6V11157961_en--_d
2018-07-24