Intended use

The device is a magnetic flux filter for heating and cooling water systems. It is used to remove magnetite particles from the system
water. The devices may be used only in systems that are sealed against corrosion and with the following water types:
Non-corrosive
Chemically non-aggressive
Non-toxic
The ingress of atmospheric oxygen into the entire heating and cooling water system, make-up water, etc. must be reliably minimized
during operation.
Note!
To ensure fault-free operation of the system for the long-term, glycols whose inhibitors prevent corrosion
phenomena must always be used for systems operating with water/glycol mixtures.
The specifications of the respective manufacturer are always decisive for the specific properties and mixing ratio of
the water/glycol mixtures.
Types of glycol must not be mixed and the concentration is generally to be checked every year (see manufacturer
information).
1.5

Inadmissible operating conditions

The device is not suited for the following conditions.
In drinking water systems
Outdoor operation
Usage with mineral oils
Usage with flammable media
For use with additives in a concentration above the permissible dosing quantity
For use with chemical substances, for which no compatibility tests have been performed for all materials present in the system
For use with water with a glycol content of greater than 50%