Controlling Theups From The Plc - Beckhoff CX1100-09 Series Hardware Documentation

Ups for embedded pcs cx10x0
Table of Contents

Advertisement

Commissioning
5.6

Controlling theUPS from the PLC

It is possible to control the UPS module from the PLC. There are two TwinCAT blocks that permit this
control. This allows the PLC program to deal with a power failure. It is, however, first necessary to make
some settings in the TwinCAT System Manager, so that the UPS can be properly included. The UPS module
is integrated in the TwinCAT System Manager, as described under Commissioning [} 27]. It is necessary,
however, for a few important settings to be made so that the PLC can obtain control. The controller must be
switched off in the System Manager. It is also necessary for the hardware inputs and outputs of the UPS to
be linked to the corresponding variables in the PLC program. The inputs and outputs must be declared in the
program as GLOBAL variables. (Further details are given below.) First the settings of the System Manager
are described.
NecessarySystem Manager settings:
-Everything must be set to OFF! In other words, on the CX1190 UPS tab, neither "Enable Automatic
Shutdown" nor "No Abort" may be activated.
-In addition, both inputs (24V State and Charge State) and both outputs (Control and DIP Control) of the
System Manager must be linked in the PLC to the UPS block in the corresponding variables.
The illustration shows the UPS being incorporated in the System Manager. The inputs and outputs of the
UPS will be found both in the process image and in the hardware image in the hierarchy browser.
The signals are associated by a double-click. This association is required in order for the function block in
the PLC program to operate properly. The PLC process image will, however, not be available until after the
program has been compiled. This means that it must be linked into a PLC program before being linked with
the UPS control block.
CX1100-09xx
Version: 1.4
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cx1100-0910Cx1100-0900Cx1100-0930Cx1100-0920

Table of Contents