Electrical Connections To A Communicating Systems Air Handler In Conventional 24V Mode - Trane ACONT900AC43UA Service Manual

Communicating residential comfort systems
Table of Contents

Advertisement

Electronic Air Cleaners
BAYTRANS12024
Transformer
• Transformer must have a grounded 120 VAC power source. Do not defeat ground plug on the transformer.
• Mount transformer to building structure with the four provided wood screws.
Note: For systems order a 120 VAC to 24 VAC transformer, KIT# BAYTRANS12024 to provide 24 volt power
only to the air cleaner. Access to 120 VAC outlet is required.
Transformer not applicable to 50 Hz units.
Figure 3

Electrical Connections To A Communicating Systems Air Handler In Conventional 24V Mode

Hazardous Voltage. Disconnect all electric power,
including remote disconnects before servicing. Fol-
low proper lockout/tagout procedures to ensure the
power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death
or serious injury.
STEP 1
Remove electrical power going into the air handler.
STEP 2
On the communicating systems air handler, remove
the blower access panel.
STEP 3
Remove the communicating control box cover.
AC - A 6
WARNING
STEP 4
Locate the red jumper wire which is attached from
EAC to R on the Communicating Systems PCB.
Confirm it is connected. If there is not a jumper wire
installed, then one must be installed in this location
in order for the air cleaner to function properly.
STEP 5
Replace the Communicating control box cover.
STEP 6
Locate the white wire coming from the Communicating
System Air Handler PCB labeled "EAC". The wire will
have a male spade terminal connected to it and a
female spade terminal inserted into the male terminal.
Remove the female spade terminal and crimp it to the
green wire on the air cleaner harness.