Eaton PKE12 Manual page 62

Motor-protective circuit-breaker / overload monitoring of ex e motors
Hide thumbs Also See for PKE12:
Table of Contents

Advertisement

Available languages

Available languages

58
Table 6:
Maximum cross-sections of motor supply cables
1- 6 mm
1 - 4 mm
UL
AWG14 - 10
Cu 75 °C
Table 7:
Assignment of minimum conductor cross-sections to
rated operational current values to EN 60947-1
Current range
[CSA]
0 - 8
8 -12
12 - 15
15 - 20
20 - 25
25 - 32
06/10 MN03402004Z-DE/EN
2
1.7 Nm
2
1.7 Nm
1.8 Nm/16 lb-in
Wire
Conductor cross-section
2
[mm
]
AWG
1.0
18
1.5
16
2.5
14
2.5
12
4.0
10
6.0
10

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Pke32

Table of Contents