Motor-protective circuit-
breaker PKE12 and PKE32
40
The tripping blocks and rated operational current must be
set on all trip blocks PKE-XTU(A)-...
With trip blocks PKE-XTUA-... operational data, such as
currents and trip causes can also be transmitted to a higher-
level fieldbus system through SmartWire-DT. This does not
affect motor protection.
h
For further information, see manual AWB2723-1613.
As of publication date 05/10 this manual has been
renamed to MN050060001Z.
It is availalbe for download on the Internet.
http://www.eaton.com/moellerproducts
h
Caution!
Combinations approved for protecting Ex e motors are
PKE12 and PKE32 with trip units PKE-XTU-....
PKE with trip units PKE-XTUA-... can not be used for
protecting Ex e motors.
Table 1:
Part no.
PKE12/XTU(A)-1.2
PKE12/XTU(A)-4
PKE12/XTU(A)-12
PKE12/XTU(A)-32
PKE setting range
Setting range I
[A]
0.3 - 1.2
1 - 4
3 - 12
8 - 32