IEC 60870-5-101 and IEC 60870-5-104
Value for (t)
Table 34:
Time monitor counter
2.22.7
Activating and Deactivating the IEC 60870-5-101 and IEC
60870-5-104 Interfaces
In order to use IEC 60870-5-101 and IEC 60870-5-104 the corresponding interfaces have to be
activated explicitly.
Also take care for IEC 60870-5-101 that the protocol is bound to a serial interface in mode
iec-101.
Commands to activate / deactivate an IEC 60870-5-101 / IEC 60870-5-104 interface
< s e t { i e c 1 0 1 | i e c 1 0 4 } i n t e r f a c e { 1 | 2 } n o s h u t d o w n >
< s e t { i e c 1 0 1 | i e c 1 0 4 } i n t e r f a c e { 1 | 2 } s h u t d o w n >
2.22.8

Setting Addresses and Address Parameters

There are degrees of freedom in respect to the protocol parameters when using IEC
60870-5-101 and IEC 60870-5-104. Typically, these are system-wide identical and have
to be adapted. This includes among others the length of the protocol data fields, the
acknowledging behaviour and the station and object addresses.
Commands to set the addresses an their lengths for IEC 60870-5-101 / IEC 60870-5-104
< s e t { i e c 1 0 1 | i e c 1 0 4 } i n t e r f a c e { 1 | 2 } s t a t i o n - a d d r e s s
{ l o c a l A S D U a d d r e s s 0 - 6 5 5 3 6 } >
< s e t { i e c 1 0 1 | i e c 1 0 4 } i n t e r f a c e { 1 | 2 } l e n g t h s t a t i o n -
a d d r e s s { 1 - 2 } >
< s e t { i e c 1 0 1 | i e c 1 0 4 } i n t e r f a c e { 1 | 2 } l e n g t h
o b j e c t a d d r e s s { 1 - 3 } >
< s e t { i e c 1 0 1 | i e c 1 0 4 } i n t e r f a c e { 1 | 2 } o b j e c t s t r u c t u r e
{ a - b - c } >
< s e t i e c 1 0 1 i n t e r f a c e { 1 | 2 } l e n g t h l i n k - a d d r e s s { 0 - 2 } >
< s e t { i e c 1 0 1 | i e c 1 0 4 } i n t e r f a c e { 1 | 2 } l e n g t h
t r a n s m i s s i o n - c a u s e { 1 - 2 } >
< s e t i e c 1 0 1 i n t e r f a c e 1 s i n g l e - c h a r a c t e r n o d a t a - t x - r x >
< s e t i e c 1 0 1 i n t e r f a c e 1 s i n g l e - c h a r a c t e r n o n e >
< s e t i e c 1 0 1 i n t e r f a c e 1 s i n g l e - c h a r a c t e r r x >
< s e t i e c 1 0 1 i n t e r f a c e 1 s i n g l e - c h a r a c t e r t x - r x >
2.22.9

Settings for the Protocol Conversion

To activate the protocol conversion, IEC 60870-5-101/-104 interfaces have to be bundled as
pairs. Then the assignment of IEC 60870-5-101 link addresses to IEC 60870-5-104 IP addresses
have to be set. Further settings include the operation of IEC 60870-5-101 interfaces as Master
and details for the protocol conversion.
72
Description
The default value for IEC 60870-5-104 is: 20 s