Drive (Right); Mounting (Right); Figure 9. Tubing According To Compressor´s Drive: Direct Drive (Left) & Belt Drive (Right) - Emerson Vilter MicroVission Retrofit Manual

Hide thumbs Also See for Vilter MicroVission:
Table of Contents

Advertisement

Step 4. Mount the MicroVission bracket to the compressor frame with four (4) 3/4" bolts and hardware provided. If the
compressor base is filled with concrete the bracket can be welded to the compressor frame. Follow standard
practices for welding and fabrication procedures.
WARNING
When handling microcontroller, use additional
personnel or lifting device as required. Failure to
comply may result in serious injury and/or damage to
equipment.
Step 5. Mount the Block & Bleed bracket with valves and hardware from KT1133A9(A10) and install the pressure
transducers as shown as in Figure 9 and Figure 10.
Mount and install 1/4" ASTM A179 steel tubing (provided by others) between pressure transducers, suction,
discharge, and oil manifold connections.
Verify correct transducer pressure ranges:*
Figure 9. Tubing According to Compressor´s
Drive: Direct Drive (Left) & Belt Drive (Right)
MicroVission Retrofit Instructions • 35391MVRF
Suction
Discharge
0-200 psia
0-414.5 psia
*0-414.5 psia intermediate on integral 2-stage compressors
Figure
10.
Direct
Transducer Mounting (left) and
Belt Drive Transducer Mounting
(right)
NOTE
If excesive vibration occurs, further support from the
controller bracket to the base may be required
Oil Manifold
0-200 psia
Drive
9

Advertisement

Table of Contents
loading