12.14 Solar Operation (Optional)

12.14.1 Solar Operation:
1
External solar heat source signal can be connect to unit for proper control of heat source switching during
tank boiling time.
2
Control according to preset whether solar priority is set or not.
3
When tank connection is NOT set at SETTING mode, solar operation is disabled.
4
When Pump A (from solar pump station) is detected On through connection Y3 and Y4, then the Solar pump
3 Way Valve is requested ON (Refer to figure below).
Connecting diagram with the Solar Pump Station
Indoor Unit
AC230V
12.14.2 Solar Operation Control
When solar priority is SET
1
Operation condition:
a 3 way valve operates if all of the following conditions are fulfilled:
Power On. (regardless operation ON or OFF)
There is operation request from solar pump station.
Tank hot water temp is below solar on upper limit temp 72°C.
2
Stop condition:
a 3 way valve stops operating when:
No power supply to unit OR
There is NO operation request from solar pump station OR
Tank hot water temp is above solar off upper limit temp 80°C.
* heat pump OFF OR operate to room side when solar pump operate during solar priority set.
* booster heater OFF when solar pump operate during solar priority set.
When solar priority is NOT SET
1
Operation condition:
a 3 way valve operates if all of the following conditions are fulfilled:
Power On. (regardless operation ON or OFF)
There is operation request from solar pump station.
Tank hot water temp is below solar on upper limit temp 72°C.
Heat pump thermo OFF in tank mode OR Heat pump operate to room side
(during operation ON and tank mode selected).
2
Stop condition:
a 3 way valve stops operating when:
No power supply to unit OR
There is NO operation request from solar pump station OR
Tank hot water temp is above solar off upper limit temp 80°C.
Heat pump thermo ON and operate to tank side. (during operation ON and tank mode selected)
communication
cable
SCB
Pump A Operation
R
IN
Signal Input
R
OUT
PWR
E
Y
3
R
IN
Y
4
Tank
R
OUT
TM200
OLP
E
65
Solar Pump Station
Pump A Operation
AC230V
Signal Output
Tank temperature sensor
for Solar pump station (Ø 8mm)
Solar pump 3 way
Valve
E