Installing The Box Pc 620 - Siemens SIMATIC Box PC 620 Getting Started

Hide thumbs Also See for SIMATIC Box PC 620:
Table of Contents

Advertisement

Recording the Serial Number and the Ethernet address
6. Enter the serial number and the Ethernet address of your PC in the table below. You can find
the serial number on the type label attached to the rear of the device. The Ethernet address can
be found in the BIOS setup settings in the main menu under the 'Hardware Options' function.
The device can precisely be identified with the help of these numbers in case of repairs or theft.
Enter the Microsoft Windows "Product Key" from the "Certificate of Authenticity"
7. Enter the Microsoft Windows "Product Key" from the "Certificate of Authenticity" (COA) in the
table. You will find the "Product Key" on the device on the power supply unit covering. You need
the Windows "Product Key" if you want to reinstall the operating system.
Serial number
Order No.
Microsoft Windows Product Key
Ethernet Address
+

Installing the Box PC 620

The Box PC 620 can be operated in several fitting positions. It is particularly suitable for fitting in
consoles, switch boards and control panels.
The Box PC 620 with AC power supply meets the requirements for a fire enclosure to EN60950. it
can therefore be fitted without an additional fire enclosure.
The Box PC 620 with DC power supply is an open device according to EN60950; therefore the
mounting must meet the requirements of a fire enclosure.
Warning
!
Only connect the device to 24V DC power supply systems which meet the requirements of a safe
extra-low voltage (SELV).
The cable cross section has to be large enough that the Box PC will not be damaged by the cables
when there is a short circuit.
Please note the following points when installing the PC:
• Avoid extreme ambient conditions as far as possible. Protect your PC from dust, moisture, and
heat.
• Keep the PC out of direct sunlight.
• Mount the PC as safely as possible to prevent any danger (for example, by falling over).
• The clearance around the housing must be at least 100 mm at the front and rear, so that the PC is
sufficiently ventilated.
• Make certain that the ventilation slots for the housing are not covered.
• Observe the permissible fitting positions without fail when installing the systems.
Warning
!
If the systems are installed in a non-permissible fitting position, the approvals pursuant to UL 1950,
UL 508 and EN60950 are no longer valid!