Mounting and operating instructions AMTRON X-50 Serie-Nr. BMEE [Internet version] Please help to ensure a long reliable service of this heat meter by carefully installing it according to the instructions. These instructions are to be given to the user or leave them near the device! M10000def.doc VD 3-248 e 03.2006...
Units loop M-Bus loop CONFIG loop (Configuration) System loop Editing methods Number entry Date entry Time entry Commissioning Commissioning Function control Error messages, alarms Data back-up Recalibration/auditing Procedure Audit modules Technical data Mounting template VD 3-248 e 03.2006 Aquametro AG...
Verify the pulse value of the flow meter and the totaliser according to the labels. Pay attention to the flow direction of the flow meter. Verifiable parameters or other service parameters can only be changed in the field if the instrument is not a verified unit. Documentation is available on request. Aquametro AG VD 3-248 e 03.2006...
Page 4
Mounting and operating instructions AMTRON X-50 Scope of supply; needed mounting material and tools 1) Option Open casing VD 3-248 e 03.2006 Aquametro AG...
Page 5
AMTRON X-50 Mounting and operating instructions Mounting on DIN rail (Mounting template, see attachment) Mounting on flat wall (Mounting template, see attachment) Aquametro AG VD 3-248 e 03.2006...
Page 6
Mounting and operating instructions AMTRON X-50 Terminal assignments see inside cover Terminal assignments VD 3-248 e 03.2006 Aquametro AG...
Page 7
Mounting and operating instructions Connect signal cables and where appropriate connect the low voltage supply Close cover Remove sealing studs These instructions are to be given to the user or leave them near the device! Aquametro AG VD 3-248 e 03.2006...
11. Clip-on holder for rail mounting 12. Cover hinge 13. Plug-in totaliser module 14. Connector module 15. Cable entry Ø12 mm with plastic seal 16. Cable entry Ø16 mm with plastic seal 17. Options module VD 3-248 e 03.2006 Aquametro AG...
Programming Mode: This can be activated only if the factory seal has been destroyed. This enables the complete range of settings, including calibrated values to be made. Aquametro AG VD 3-248 e 03.2006...
- Press Service key S-Edit - Press Enter key - Entry according to type of data Edit in Programming Mode: Prog - Press Service key P-Edit - Press Enter key - Entry according to type of data VD 3-248 e 03.2006 Aquametro AG...
Display test Test InStAnt Instantaneous values tIME Time parameters Stich Billing date LOGGEr Logger data InPutS Input signal parameters OutPutS Output signal parameters UnitS Units M-bUS M-Bus parameters CONFIG Configuration parameters SYStEM Manufacturing parameters Aquametro AG VD 3-248 e 03.2006...
The Instant loop shows the current values. InStAnt 60.0 °C Temperature on hot side 40.0 °C Temperature on cold side ∆T 20.00 °C Temperature difference 0.025 MW Power 6.5 m3/h Volume rate 1.156 C-Factor 0.991 KG/L Density of fluid VD 3-248 e 03.2006 Aquametro AG...
Volume flow reading on billing date 12345.678 m3 Memory Reading of auxiliary counter 2 on billing date H2 12345.678 m3 Memory Reading of auxiliary counter 3 on billing date H3 12345.678 m3 Memory Hours of error till billing date Aquametro AG VD 3-248 e 03.2006...
Note: Before adjusting the pulse value, you have to choose the unit in the units loop. Settings of the main input (No.1) are verifiable. They can only be changed if the seal is broken [P-Edit]. VD 3-248 e 03.2006 Aquametro AG...
Page 15
Built in warm side Input number (2 & 3) InPutS Auxiliary input HELP Value of a pulse 1.000 L S-Edit Maximum input frequency = 10Hz 10 Hz ON: Closed contact Off: Open contact Aquametro AG VD 3-248 e 03.2006...
Page 17
0.001, 0.01, 0.1, 1 MBT=MBtu MJ/h Possible settings GJ/h KB/h=kBtu/h MB/h=MBtu/h m3/h m3/h Possible settings GA/h=USgal/h °C °C Possible settings °F EP Pro PULS KWh Possible settings KBT=kBtu Possible settings VP Pro PULS L GAL=USgal M2040def.doc Aquametro AG VD 3-248 e 03.2006...
Reset of alarms and counters CANCEL S-Edit Temperature difference below which no further energy is 1.55 K 0 ... 2.99 K/°R S-Edit counted. The unit for ºC is K and for ºF it is ºR VD 3-248 e 03.2006 Aquametro AG...
Page 19
Service Program Non verifiable data All parameters — CANCEL Reset of alarms and counters according the CANCEL ALArM authorization in the table below CountEr Mode User Service Program Cancel Reset Alarm Reset Counter M2350e Aquametro AG VD 3-248 e 03.2006...
Finish the entry with the Enter key The values and digits can be adjusted in their possible range from 1 to 8 digits between 0 and 9. Partly the sign (+/-) can be set. VD 3-248 e 03.2006 Aquametro AG...
Check the current values of the running installation, if plausible values are shown (see Instant loop). In the Config loop the reset time (to zero) of the display and the filter properties of the current values of Q and/or P can be adjusted. Aquametro AG VD 3-248 e 03.2006...
The device has the advantage that only the totaliser module has to be returned. The field wiring can remain con- nected. Due to the integrated configuration memory in the connecting board, the measuring point data remain (this does not apply to calibration data) . VD 3-248 e 03.2006 Aquametro AG...
Type of sensor connection required Sensor cable, length tested and certified till Display kWh, MWh, MJ, GJ, kBtu, MBtu Display units , USgal kg, t Display capacity Post decimal positions 88'888'888 0, 1, 2, 3 Aquametro AG VD 3-248 e 03.2006...
Page 24
10 Hz, 3V / 2.2MΩ Maximum frequency 6 Hz at a duty cycle 50% ≥ 8 ms Minimum impulse length ≥ 80 ms Minimum length of a break Open Collector transistor or mechanical contact External wiring M3340e VD 3-248 e 03.2006 Aquametro AG...
Page 25
AMTRON X-50 Mounting and operating instructions Notes: Aquametro AG VD 3-248 e 03.2006...
Page 26
Mounting and operating instructions AMTRON X-50 Notes: VD 3-248 e 03.2006 Aquametro AG...