9. Check list

If all questions in the below check list are answered with "yes", it can be assumed that the
is installed correctly. The check list can be downloaded from
Checklist for HVI
Address of the test object:
Name:
Contact partner:
Street:
Postcode, Place:
Phone:
Item Question
1
Is the whole system positioned in the protected area?
2
Has the separation distance been calculated?
(down conductor to the earth-termination system, isolated system with connection to existing
external lightning protection system or lightning equipotential bonding on roof level)
3
of the HVI
HVI
HVI
HVI
4
Is the calculated separation distance kept in the range of the sealing end?
5
Is the supporting tube and, if required, the equipotential bonding element of the sealing end
correct, i.e. only connected with the equipotential bonding / the lightning equipotential bond-
ing of the system?
6
Is the minimum distance of 0.2 m kept between HVI
connection to opposite down conductors been considered?
7
Has the minimum bending radius been kept?
HVI
HVI
HVI
HVI
8
Is the equipotential bonding element of the sealing end in contact with the semiconductive
layer (not grey coating)?
9
Has the supplementary information in DEHN installation instructions No. 1501/No.1892
been considered for installation of the HVI
10 Did you exclusively use (tested) components of the manufacturer DEHN + SÖHNE?
Conductor kept?
®
light Conductor / DEHNcon H
®
Conductor
®
®
power Conductor
light Conductor (dark grey outer coating)
®
Conductor (black outer coating)
®
Conductor (grey outer coating)
®
power Conductor (black outer coating)
®
Place
Signature of tester
www.dehn-international.com.
Installation
®
s ≤ 0.45 m in air
s ≤ 0.9 m solid material
s ≤ 0.75 m in air
s ≤ 1.5 m solid material
s ≤ 0.9 m in air
s ≤ 1.8 m solid material
®
Conductors routed in parallel and has the
200 mm
200 mm
230 mm
270 mm
/HVI
power Conductor in hazardous areas?
®
®
Company
Date
14
HVI
Conductor
®
Rating
YES
NO
DEHN Form No. 2848/E/0815
Publication No. 1565 / UPDATE 04.18