Note: These notification appliances are UL Listed as "Special Application." They are intended to be used only with Siemens notification appliance circuits.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM'S
PRIMARY AND SECONDARY POWER SOURCES DO NOT EXCEED THE POWER SOURCES' RATED CAPACITY OR THE CURRENT RATINGS OF
ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE
RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
CANDELA AND SOUND OUTPUT SETTINGS:
To set the candela, slide the switch to the desired setting. The setting is indicated by the pointer and label visible on the bottom side of the lens.
WARNING: THE AUDIBLE STROBE APPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE
THEY ARE INSTALLED. THIS IS DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE INSTRUCTIONS.
Figure 3:
Jumper plug settings for High, Medium, Low and Code 3
HI
MED
LOW
(Use needle nose pliers to pull and properly set the jumper plugs)
NOTE: The AS-HMC must be set for Code 3 (or March Time) when used with a synchronized notification appliance circuit (NAC).
Siemens Building Technologies, Inc.
Table 3: Current Ratings (AMPS)
Maximum RMS Current with Hi dBA Setting
Voltage
DC
16.0-33.0VDC
FWR
16.0-33.0VRMS
Maximum RMS Current with Med dBA Setting
Voltage
DC
16.0-33.0VDC
FWR
16.0-33.0VRMS
Maximum RMS Current with Low dBA Setting
Voltage
DC
16.0-33.0VDC
FWR
16.0-33.0VRMS
Figure 1:
135
185
CANDELA
POINTER

BOTTOM VIEW

Factory setting is on Medium dB, Code 3 (or March Time) and 185 candela.
(or March Time)
SHOWN SET ON HIGH dB
SHOWN SET ON MED dB
SHOWN SET ON LOW dB
135cd
185cd
0.356
0.488
0.499
0.705
135cd
185cd
0.361
0.493
0.509
0.716
135cd
185cd
0.356
0.499
0.488
0.705
Figure 2: Showing Location of Jumper Plug
CODE 3
CANDELA
SLIDE
SWITCH
HI
MED
LO
BACK VIEW
Figure 4:
Jumper plug setting for Continuous Horn
CODE 3
No jumper plug is needed for continuous horn setting.
However, it is recommended that the jumper plug be retained in
the unit for future use (if needed) as shown in Figure 4.
TURN PLUG 90°
P84449-003 B
Sheet 2 of 4