Installer Connections - IDEAL EVOMAX 2 Series User Manual

Table of Contents

Advertisement

3.

INSTALLER CONNECTIONS

Mains Voltage/230V 50Hz
I1
I2
1
2
3
1
L
N
PE
SL1
Mains Supply
Volts Free Contacts
I5
1
2
3
4
5
6
C
NO
PE
C
NO
PE
MFR1
MFR2
I7
I8
1
2
1
2
I0
I1
PWM GND
PELV
Interlock
Pump control
PELV Only
I7 Optional Interlock input.
I8 Optional Pump Modulation Control, 0-10V.
I9 Boiler Control:
0-10V Capacity or Temperature.
OpenTherm Interface 1. Boiler, Heating Circuit 1 and/or
DHW Circuit Control.
OpenTherm Interface 2. Heating Circuit 2 Control.
*Note: The items grayed out are not standard and are connections provided by the relevant option kits.
I3
2
3
4
1
L
SL2
L
~
230V 50Hz
Demand inputs
Interlock
I6
1
2
3
4
C
NO
C
NO
MFR3
MFR4
PELV
I9
3
1
2
3
10V
10V
GND
OT1+ OT1- OT2+ OT2-
0-10V
KEY
I4
2
1
2
~
L
N
230V 50Hz
Auxiliary
I10
4
5
6
1
2
S1
GND
OpenTherm
Header
I10 Optional Sensors:
Header Sensor for Cascade Control.
DHW Tank Temperature or Heating Circuit 2 Room
Temperature.
Heating Circuit 1 Room Temperature.
Outside Temperature Sensor for Heating Curve.
20
KEY
l1 Mains Supply Connector, 230V
50Hz. Live, Neutral, PE.
l2 Demand inputs,
Multifunctional, 230V 50Hz.
Typical setting:
SL1, Heating Circuit 1
SL2, Heating Circuit 2/DHW
l3 Optional Interlock input, 230V
50Hz
l4 Auxiliary Mains Supply Output,
230V 50Hz. Live, Neutral.
KEY
I5 Multifunction Volts Free Relay
Outputs, 24V DC to 230V
50Hz. Typical setting:
MFR1 Heating Circuit 1 Pump
MFR2 DHW Circuit Pump
I6 MFR3 Burner On Indication
MFR4 Boiler Fault Indication
3
4
5
6
7
8
S2
GND
S3
GND
S4
GND
DHW Tank /
Outside
Room 2
Room 1
Temp.

Advertisement

Table of Contents
loading

Table of Contents