2.3 System layout WKF/WKF-compact 180

GRL
VWW
NIM
NZ1
Fig. 3: System layout WKF/WKF-compact 180
AB:
Outdoor area
IB:
Indoor area
AM1,2: Outdoor module WKF-compact 180, WKF
180
IM1,2: Indoor module WKF-compact 180, WKF 180
GRL:
Common return pipe (DN 25)
KA1:
Condensate drain OM (must be designed to
be frost proof!)
KA2:
Condensate drain IM
KML:
Refrigerant lines
NAM:
Mains supply OM = 400V / 3~ / 50Hz
3x16 A (e.g. 5x1,5 mm
VHZ
IM1
STL
KML
AM1
VEN
VEN
NAM
KA1
3
5
/
" and
/
"
8
8
2
)
NIM
NZ2
KA2
IB
AB
NIM:
Mains supply IM = 230V / 1~ / 50Hz
16A (e.g. 3x1,5 mm
NZ1:
Mains cable electric auxiliary heater (e.g.
5x2,5 mm
2
)
NZ2:
Mains cable electric auxiliary heater
(optional), (e.g. 5x2,5 mm
STL:
Control cable sheathed (e.g. 2x1mm
VEN:
Fan
VHZ:
Inlet for heating (DN 32)
VRH:
Hot-water inlet and return pipes (DN 32)
VWW: Inlet pipe for hot-water tank (DN 32)