Electrical wiring REMKO series WKF NEO-compact Smart heat pumps Air/water system for heating or cooling WKF NEO-compact 70, WKF NEO-compact 120, WKF NEO-compact 180 Instructions for Technicians 0188-2019-04 Edition 3, en_GB Read the instructions prior to performing any task!
Page 2
Read these operating instructions carefully before commis- sioning / using this device! These instructions are an integral part of the system and must R410A always be kept near or on the device. Subject to modifications; No liability accepted for errors or mis- Refrigerant prints! Translation of the original...
Table of contents Safety and usage instructions......................4 1.1 General safety notes........................4 1.2 Identification of notes........................4 1.3 Personnel qualifications........................4 1.4 Dangers of failure to observe the safety notes................4 1.5 Safety-conscious working....................... 4 1.6 Safety notes for the operator......................5 1.7 Safety notes for installation, maintenance and inspection..............
REMKO series WKF NEO-compact Safety and usage instructions CAUTION! This combination of symbol and signal word 1.1 General safety notes warns of a potentially hazardous situation, which if not avoided may cause injury or mate- Carefully read the operating manual before com- rial and environmental damage.
"certificate of warranty" to with all applicable regional regulations. REMKO GmbH & Co. KG at the time when the Local regulations and laws such as Water units are purchased and commissioned.
REMKO series WKF NEO-compact 1.11 Transport and packaging The devices are supplied in a sturdy shipping con- tainer. Please check the equipment immediately upon delivery and note any damage or missing parts on the delivery and inform the shipper and your contractual partner.
Electrical wiring 2.1 System layout WKF NEO 70 Fig. 1: System layout WKF NEO 70 A: Outdoor area Outdoor unit B: Indoor area 2a: Fan Indoor unit 2b: Power supply, outdoor unit 1a: Heating inlet flow (1 " AG) = 230V/1~/50Hz, 16A (e.g. 3 x 2.5 mm 2c: Condensate tray, outdoor unit 1b: Heating return flow (1 "...
REMKO series WKF NEO-compact 2.2 System layout WKF NEO 120 Fig. 2: System layout WKF NEO 120 A: Outdoor area Outdoor unit B: Indoor area 2a: Fan Indoor unit 2b: Power supply, outdoor unit 1a: Heating inlet flow (1 " AG) = 230V/1~/50Hz, 20A (e.g.
2.3 System layout WKF NEO 180 Fig. 3: System layout WKF NEO 180 A: Outdoor area Outdoor unit B: Indoor area 2a: Fan Indoor unit 2b: Power supply, outdoor unit 1a: Heating inlet flow (1 " AG) = 400V/3~/50Hz, 3 x 16A (e.g. 5 x 1.5 mm 2c: Condensate tray, outdoor unit 1b: Heating return flow (1 "...
REMKO series WKF NEO-compact The indoor and outdoor units have to be connected with refrigerant lines of dimensions (outer diam- WARNING! eter) "(=9.52 mm) and "(=15.88 mm). At least a two-wire control line has to be laid between the All electric lines are in accordance VDE regula- two modules.
Page 11
WKF NEO 180 400V/3~/N/Pe 230V~/N/Pe 400V/3~/N/Pe L1 N Pe L1 L2 L3 N Pe L1 L2 L3 N Pe Fig. 5: Overview of electrical cables 1: Main distribution A: Power supply outdoor unit B: Power supply indoor unit C: Power utility disable signal, potential-free / open = AM locked D: Power supply heating coil, 6 kW indoor unit E: Communication F1/F2 outdoor unit / indoor unit...
REMKO series WKF NEO-compact 2.5 Electrical connection general notes WARNING! It is necessary to lay a mains cable both to the All cable sizes are to be selected according to outdoor unit and, separately, to the indoor unit. VDE 0100. Special attention should be given to...
2.6 Electrical connection - indoor unit The following instructions describe the electrical At the site, avoid adding cable inlets. connection of the indoor units. Remove the housing from the upper section by pressing it upwards and pulling it forwards 2.7 Electrical connection - out of the rear groove.
Page 14
REMKO series WKF NEO-compact When connecting the control line, make sure that polarity is correct. If the outdoor unit is installed on a roof, it and the supporting structure must be earthed sepa- rately (connection to lightning conductors or foundation earth/ground feature).
Page 15
Contact probe External probe Contact probes can be mounted on the pipes, to The connection of an outdoor sensor is always measure the heating-circuit temperatures, for required for Smart Control Touch. example. Mount the external probe pointing skyward, in The contact probes are fastened to a pipe with a north-easterly direction, about 2.5 metres the trapezoidal brackets and retaining strap above the ground.